Fault Codes THERMA V
HVAC Service App zur Fehlerdiagnose, Reparatur und Wartung
|
|
Schritt-für-Schritt zur Lösung Immer Up-to-date Fehlercodes eingeben Weitere Features Konto einrichten |
|
|
|
|
Hol dir jetzt die HVAC App für iOS und Android! |
||
Fehlermeldungen optisch
FEHLERCODE | BESCHREIBUNG | ANZAHL DER BLINKIMPULSE | |
INNENGERÄT | |||
LED 1 | LED 2 | ||
01 | Innengerät Fehler Raumtemperatursensor | 1 mal | - |
02 | Innengerät Fehler Sensor Verdampfer Eintritt | 2 mal | - |
03 | Fehler Kabelfernbedienung | 3 mal | - |
04 | Fehler Schwimmerschalter (optional) | 4 mal | - |
05 | Kommunikationsfehler zwischen Innen- und Außengeräten | 5 mal | - |
06 | Innengerät Fehler Sensor Verdampfer Austritt | 6 mal | - |
09 | Innengerät Fehler EEPROM | 9 mal | - |
10 | Innengerät BLCD Motor Lüfter blockiert | - | 1 mal |
12 | Innengerät Fehler Sensor Verdampfer Mitte | 2 mal | 1 mal |
Wiederstandswerte der Thermistoren
LUFTSENSOR (RAUMFÜHLER UND AUSSENLUFTFÜHLER) | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Temp. | -20°C | -15°C | -10°C | -5°C | -2°C | 0°C | 2°C | 5°C | 10°C | 15°C | 18°C | 20°C | 22°C | 24°C |
kΩ | 105 | 80,2 | 58,2 | 44,0 | 37,4 | 33,6 | 30,3 | 25,9 | 20,2 | 15,8 | 13,8 | 12,5 | 11,4 | 10,5 |
Temp. | 25°C | 26°C | 28°C | 30°C | 32°C | 34°C | 36°C | 38°C | 40°C | 50°C | 60°C | 70°C | 80°C | 90°C |
kΩ | 10 | 9,57 | 8,76 | 8,0 | 7,38 | 6,78 | 6,24 | 5,74 | 5,3 | 3,59 | 2,49 | 1,76 | 1,27 | 0,93 |
VERDAMPFERFÜHLER / ROHRANLEGESENSOR | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Temp. | -20°C | -15°C | -10°C | -5°C | -2°C | 0°C | 2°C | 5°C | 10°C | 15°C | 18°C | 20°C | 22°C | 24°C |
kΩ | 52,7 | 38,9 | 29,1 | 22,0 | 18,7 | 16,8 | 15,1 | 13 | 10,1 | 7,92 | 6,88 | 6,27 | 5,72 | 5,23 |
Temp. | 25°C | 26°C | 28°C | 30°C | 32°C | 34°C | 36°C | 38°C | 40°C | 50°C | 60°C | 70°C | 80°C | 90°C |
kΩ | 5,00 | 4,78 | 4,38 | 4,0 | 3,69 | 3,39 | 3,12 | 2,87 | 2,65 | 1,79 | 1,24 | 0,88 | 0,64 | 0,47 |
HEISGASSENSOR | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Temp. | 1°C | 5°C | 10°C | 15°C | 20°C | 25°C | 30°C | 35°C | 40°C | 45°C | 50°C | 55°C | 60°C | 65°C |
kΩ | 525,00 | 448,00 | 326,00 | 294,33 | 242,20 | 200,00 | 167,57 | 138,03 | 133,80 | 98,00 | 82,00 | 64,50 | 59,00 | 50,71 |
Temp. | 70°C | 75°C | 80°C | 85°C | 90°C | 95°C | 100°C | 105°C | 110°C | 115°C | 120°C | 130°C | |
kΩ | 43,73 | 37,35 | 32,20 | 228,16 | 24,60 | 21,37 | 18,50 | 16,60 | 14,50 | 13,30 | 12,80 | 10,80 |