Euro Line EFUDO

Euro Line compressor unit *FU* regulated EFU1-DO-3 HI241CC+CIMR-AC40018F

Order No.: 115.8223
Manufacturer number: A08-100003
Manufacturer: SCHIESSL

To previous product 115.8203

More in this category: Euro Line EFUDO

Loading

One click to the most important information:

Description

Frequency-regulated Dorin compressor units work using a HI series semi-hermetic compressor. These units have been specially developed for use in refrigeration systems with variable refrigeration demand. The use of a Power Electronics Yaskawa frequency converter allows compressors to run ...

Frequency-regulated Dorin compressor units work using a HI series semi-hermetic compressor. These units have been specially developed for use in refrigeration systems with variable refrigeration demand. The use of a Power Electronics Yaskawa frequency converter allows compressors to run continuously while optimally adjusting cooling performance to the current conditions. These compressor units are therefore an energy-efficient and space-saving alternative to power racks with multiple compressors.


The Dorin compressor units are available in four different performance classes. Refrigerants R134a, R450A/R513A can be used. The maximum frequency may be limited for air conditioning applications. Cooling power is regulated depending on the intake pressure. A Power Electronics Yaskawa frequency converter is used in combination with a pressure transmitter to control the compressor unit. This is mounted and thermally decoupled on the intake side and records the actual intake pressure value. The power rack controller regulates the cooling power of the rack so that the target value is achieved as closely as possible.


The frequency converter is included with the control box. Configuration is input via a keyboard. The frequency convertor comes pre-configured. Only a small number of parameters must be changed to make changes to the refrigerant used and the place of use. The control box is mounted to the frame and wired. If there is a fault with the frequency converter, it is possible to manually switch to a temporary emergency operating mode via an additional low pressure switch.


The control box issues an isolated release signal to control solenoid valves in the fluid line. In the event of a system fault, this release is deactivated in order to prevent damage from fluid hammering when restarting the system All components are mounted to a tough riveted steel profile frame. All parts of the frame have a double coating. The power rack stands on the supplied rubber-bonded metal base. Refrigeration lines are conveniently grouped together at the rear and can be shut off.
Power racks are fitted with an oil separator as standard in order to ensure reliable operation, even during a temporary minimal cooling load on the system.

show more


Features

  • optimally adapt compressor performance to changing loads on the refrigeration system
  • low minimum cooling power
  • optimal temperature and quality for refrigerated goods
  • minimal space needed due to compact design
  • energy saving from better performance control in optimal evaporating temperatures
  • standard ...
  • optimally adapt compressor performance to changing loads on the refrigeration system
  • low minimum cooling power
  • optimal temperature and quality for refrigerated goods
  • minimal space needed due to compact design
  • energy saving from better performance control in optimal evaporating temperatures
  • standard components and simple to replace compressors mean it is easy to service
  • reduce the installed cooling power and thus the cost of investment by use of coincidence factor
  • simple installation of a heat recovery systems using a common heat exchanger for all areas to be cooled

show more


Scope of delivery

  • Control box with Power Electronics frequency converter, installation and wired
  • semi-hermetic compressor from Dorin with crankcase heater
  • compressor shut-off valves
  • fluid collector
  • refrigerant dryer / inspection glass
  • filling valve in the fluid line
  • ball shut-off valve in the pressure, fluid and ...
  • Control box with Power Electronics frequency converter, installation and wired
  • semi-hermetic compressor from Dorin with crankcase heater
  • compressor shut-off valves
  • fluid collector
  • refrigerant dryer / inspection glass
  • filling valve in the fluid line
  • ball shut-off valve in the pressure, fluid and suction lines
  • pressure transmitter, suction pressure -0.5 - 7 bar
  • pressure transmitter, high pressure 0 - 30 bar
  • combined high/low pressure monitor, type tested
  • low pressure switch, type tested for emergency operation
  • oil separator with inspection glass and shut-off valve in the return line, with electrical heating

show more


Accessories / Replacement parts

  • Control box
    control cabinet heating self-regulating 30W 230V f. EFUBO control cabinet
    Order No.: 272.1936
  • Filter insert
    Alco filter insert A3F 009909
    Order No.: 251.0276
  • Frequency convertor
    Power Electronics frequency convertors IP20 CIMR-AC4A0018FAA 14,8A Serie A1000
    Order No.: 297.9731
  • Intake pipe filter
    Alco suction line filter - dryer housing BTAS-39 1-1/8" solder 015355
    Order No.: 251.0293

Technical data

Dimensions
Width
910 mm
Height
1600 mm
Depth
670 mm
General information
Number of compressors
1 pcs
Type
Halbhermetisch
Manufacturer
Dorin
Schaltschrank aufgebaut
Ja
Type
EFU-1DO-3
Electrical Data
Supply voltage
400/3/50 V/Ph/Hz
max. operating current
12,0 A
Weight
Weight net
220 kg
Performance data
Frequency controlled
Ja
Performance data Euro Line
max. refrigerating capacity
4300 W
with R134a t0 = -10°C
min. refrigerating capacity
950 W
with R134a t0 = -10°C
Pipe connections
Pressure line
16 mm
Liquid line
12 mm
Condensate line
16 mm
Suction line
28 mm
Collector data
Receiver content
20 l
Sound data
Sound power
68,0 dB(A)
at 50 Hz
Compressor data
Compressor type
HI241CC