two pipe system

Mitsubishi air conditioner outdoor unit City Multi PUHY-HP400 YSHM-A Zubadan

Mitsubishi Electric Logo
Order No.: 719.4151
Manufacturer number: PUHY-HP400 YSHM-A
Manufacturer: Mitsubishi

One click to the most important information:

Description

The R2 series has been developed for promote energy-saving and environmentally friendly systems for use in modern buildings. The R2 series is the world’s only heat recovery system that allows simultaneous heating and cooling with just two pipes. The central components in each R2 system is ...

The R2 series has been developed for promote energy-saving and environmentally friendly systems for use in modern buildings. The R2 series is the world’s only heat recovery system that allows simultaneous heating and cooling with just two pipes. The central components in each R2 system is the BC controller - a refrigerant distributor that forms a single refrigeration and control unit with the outdoor device and thus enable heat recovery to take place. The BC controller allows up to 50 indoor units to be connection with one outdoor unit with just two pipelines.

show more


Features

  • Each indoor unit can operate independently in either heating or cooling mode
  • Heat recovery up to 100%
  • No refrigerant distributor required

Scope of delivery

  • 1x Mitsubishi Klima Außengerät City Multi PUHY-HP400 YSHM-A Zubadan

Accessories / Replacement parts

  • Required distributor set
    Mitsubishi City Multi distributor set CMY-Y100 VBK2 f.2xPUHY
    Order No.: 719.2366

Technical data

Dimensions
Width
1870 mm
Height
1710 mm
Depth
760 mm
General information
Connectable indoor units
1 - 34
Application
Kühlen und Heizen
Type
VRF
Construction
Außengerät
Refrigerant
R410A
Amount of refrigerant
18,00 kg
max. height difference
indoor unit/outdoor unit
50 m
zul. Leitungslänge
(min. - max.)
300 m
Electrical Data
Nennbetriebsstrom
Heizen
21,40 A
Kühlen
20,60 A
Supply voltage
400/3/50 V/Ph/Hz
Weight
Weight net
440,0 kg
Performance data
COP
3,74
EER
3,49
Nominal heating capacity
50,00 kW
Nominal cooling capacity
45,00 kW
Pipe connections
Liquid line
16 mm
Gas line
28 mm
Sound data
Sound pressure level
Heating VRF AU
59,0 dB(A)
explanation 1
Cooling VRF AU
59,0 dB(A)
explanation 1
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.