Rack controller AK-PC 781A with heat recovery function (24 V AC). The AK-PC 781A is a complete control unit for regulating the performance of compressors and condensers in refrigeration and air conditioning systems. The controller features oil control, heat recovery functions and CO2 gas ...

Rack controller AK-PC 781A with heat recovery function (24 V AC). The AK-PC 781A is a complete control unit for regulating the performance of compressors and condensers in refrigeration and air conditioning systems. The controller features oil control, heat recovery functions and CO2 gas pressure regulation. Controllers can also send signals for informing other controllers about operating status, e.g. forced closure of expansion valves, alarm signals and alarm messages. The primary function of the controller is to ensure that compressor and condensers are always operating under optimal pressure conditions for best energy efficiency. Both the intake pressure and the condensing pressure are controlled via voltage signals sent out by pressure transducers. Performance control can be achieved via intake pressure P0, medium temperature S4 or using a separate control pressure Pctrl (in cascades).

show more


Features

• Control performance of up to 10 compressors

• Up to 3 relief valves per compressor

• Oil management. Joint or individual control of all compressor oil valves. Collector pressure regulation.

• Speed control for 1 or 2 compressors

• Up to 6 safety inputs per compressor

• Option to ...

• Control performance of up to 10 compressors

• Up to 3 relief valves per compressor

• Oil management. Joint or individual control of all compressor oil valves. Collector pressure regulation.

• Speed control for 1 or 2 compressors

• Up to 6 safety inputs per compressor

• Option to limit performance in order to minimise consumption spikes

• If compressors cannot be started, other controllers can be informed of this and electrical expansion valves closed.

• Regulation of fluid injection into the intake line

• Start/stop fluid injection in the heat exchanger (cascade)

• MT/LT coordination between controllers in cascades

• Safety monitoring for high pressure / low pressure / pressure pipe temp.

• Performance control of up to 8 fans

• Floating target value based on external temperature

• Heat recovery function

• CO2 gas cooler and collector regulation

• Parallel compressors in transcritical CO2 systems

• Selective operation, speed regulation or combination

• Safety monitoring of fans

• Status of inputs and outputs indicated by LEDs on the front of the device.

• Alarm signals can be generated by data communication.

• Alarms with text display so that the meaning of the alarm is clear.

• Other functions that are totally separate from regulation features – these include alarm, thermostat and pressure switches and a

PI regulation function.

show more


Accessories / Replacement parts

  • Connection cable
    Danfoss cable f. EKA163/164/165 2 meter 084B7298
    Order No.: 231.0826
  • Danfoss cable f. EKA163/164/165 6 meter 084B7299
    Order No.: 231.0827
  • Danfoss plug 3+E (female) with cable f. AKS cable 5m 060G1034
    Order No.: 231.0471
  • Console
    Danfoss console AP f. EKA163/164/153 084B8584
    Order No.: 231.0828
  • Display
    Danfoss Display with operation MMIGRS2 SP 080G0294
    Order No.: 231.040347
  • Danfoss Gateway MMIMYK 080G0073
    Order No.: 231.040348
  • Danfoss display EKA 163B 084B8574
    Order No.: 231.0559
  • Danfoss display with buttons EKA 164B 084B8575
    Order No.: 231.0560
  • Pressure transmitter
    Danfoss pressure transmitter ratiometric AKS 2050 -1/+99bar 060G5751
    Order No.: 231.0768
  • Danfoss pressure transmitter ratiometric AKS 2050 -1/+159bar 060G5752
    Order No.: 231.0769
  • Danfoss pressure transmitter ratiometric AKS 32R -1/+34bar 060G0090
    Order No.: 231.0517
  • Danfoss pressure transmitter 7/16" UNF AKS 33 -1/+34bar 4-20mA 060G2051
    Order No.: 231.0747
  • Danfoss pressure transmitter ratiometric AKS 2050 -1/+59bar 060G5750
    Order No.: 231.0767
  • Probe / sensor
    Danfoss temperature sensor with cable AKS 11 Pt1000 3,5m 084N0003
    Order No.: 231.0422
  • Danfoss temperature sensor with cable AKS 11 Pt1000 5,5m 084N0005
    Order No.: 231.0423
  • Danfoss temperature sensor with cable AKS 11 Pt1000 8,5m 084N0008
    Order No.: 231.0424
  • Danfoss temperature sensor with cable AKS 12 Pt1000 1,5m 084N0036
    Order No.: 231.0460

Technical data

General information
Type
Verbundregler/Leistungsregler
Mounting type
DIN-Schiene
Approval
EU Niederspannungsrichtlinie und EMV- Anforderungen werden eingehalten.
Electrical Data
Outputs
Solid State Ausgänge:
 
 
Zur Anwendung bei häufig
Max. 240 V a.c., Min 48 V a.c.
 
geschalteten Belastungen
Max. 0,5 A
 
z.B. Öl-Ventile, Lüfter oder AKV-
Leakage < 1 mA
 
Ventil
Max. 1 AKV
Input
Analog
11 analoge Eingänge:
 
 
Pt 1000 Ohm / 0°C
Auflösung: 0,1°C
 
Genauigkeit: +/-0,5°C
 
+/-0,5°C zwischen -50°C und +50°C
 
+/-1°C zwischen -100°C und -50°C
 
+/-1°C zwischen +50°C und +130°C
 
Druckmessumformer Typ AKS
Auflösung: 1mV
 
32R / AKS 2050/MBS 8250
Genauigkeit: +/- 10 mV
 
AKS32 (1-5V)
Max. Anschluss von 5 Druckmessumformer an ein Modul
 
Andere Druckmessumformer
 
Radiometrisches Signal
 
Spannungssignal 0 - 10V
 
Kontaktfunktion (EIN/AUS)
EIN bei R < 20 Ohm
 
AUS bei R > 2 kOhm
 
Digital
8 digitale Ausgänge
4 Solid state-Ausgänge und 4 Relaisausgänge
Power consumption
8 VA
Relay outputs
SPDT:
 
AC-1 (ohmisch)
4A
 
AC-15 (induktiv)
3A
 
U
Min. 24V
 
Max. 230V
Protection class
IP10
VBG 4
Supply voltage
230/1/50 V/Ph/Hz
24 V DC/ AC +/- 20 %
Weight
Weight net
0,6 kg
Temperature data
Temperature measuring range
max.
70 °C
min.
-20 °C
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.