- Products
- JCI gas warning sensor f. Hotel & Office RMV-HFC: 12-24VAC, IP21
Warning systems
JCI gas warning sensor f. Hotel & Office RMV-HFC: 12-24VAC, IP21
Icon. Image similar to product.
Icon. Image similar to product.
Order No.: 476.2272
Manufacturer number: RMV-HFC
Manufacturer: Johnson Controls
To subsequent product 476.4079
One click to the most important information:
Description
- Can be used for all HFC and HFCFC gases
- Failsafe function
- Two factory-set alarm thresholds
- Adaptive alarm time delay
- LED (4) display for operating status, function test and alarm
- Integrated buzzer (3), can be deactivated
- Alarm relay (SPDT) output, bundled with relays in normal operation
FUNCTION
When ...
- Can be used for all HFC and HFCFC gases
- Failsafe function
- Two factory-set alarm thresholds
- Adaptive alarm time delay
- LED (4) display for operating status, function test and alarm
- Integrated buzzer (3), can be deactivated
- Alarm relay (SPDT) output, bundled with relays in normal operation
FUNCTION
When the power supply is switched on, the LED (4) begins to flash alternately green / red and the relay is activated.
After five minutes the LED (4). Changes display green light, which indicates normal operation.
LOW VOLTAGE DIRECTIVE
This product complies with the Low Voltage Directive 2006/95 /EEC and the EMC Directive 2004/95/EEC.
It meets the requirements according to:
EN 61 000-6-2:2001
EN 61 000-6-3:2001
EN 61 000-3-2:2001
EN 61 000-3-3:1995
EN 61 010-1:2001
Technical data
Dimensions
Width
89 mm
Height
44 mm
Length
89 mm
General information
Connection terminals
5 x 2,5 mm²
Housing
Weißer Kunststoff
Refrigerant
alle HFC und HFCKW Gase
Electrical Data
Power consumption
100 mA
normal 40 mA
Relay outputs
Max 1,0 A (30 V DC)
or 0,5 A (125V AC), SPDT
Supply voltage
12 bis 24 V
Humidity
Relative humidity
0 bis 95 %
non-condensing
Weight
Weight net
0,09 kg
Sound data
Sound power
85 dB(A)
2300Hz (+ - 300Hz)
Temperature data
Operating range
0 bis 50 °C
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.