Reciprocating piston

Dorin compressor H2 H380SB-E w.Klixon 400V

Order No.: 112.4581
Manufacturer number: H2P0361
Manufacturer: Dorin

To previous product 112.4234

More in this category: Reciprocating piston

Loading

One click to the most important information:

Description

The semi-hermetic compressors from Dorin have been developed to meet the requirements of new refrigerants and meet market demands where energy-efficiency, reliability and minimal noise emissions are key aspects. This series covers capacities from 4.52 to 244.78 m3/h at rated powers from 0.5 hp ...

The semi-hermetic compressors from Dorin have been developed to meet the requirements of new refrigerants and meet market demands where energy-efficiency, reliability and minimal noise emissions are key aspects. This series covers capacities from 4.52 to 244.78 m3/h at rated powers from 0.5 hp to 90 hp.

The quality of all Dorin products is guaranteed by their EN ISO 9001 certified quality management system. Models with UL certification are available on request.

show more


Features

  • High performance (COP) thanks to optimised internal media flow dynamics, the use of high-performance motors and the introduction of the latest generation of components
  • Operation with all conventional refrigerants: R448A/R449A, R404A/R507A, R134a, R407C, R407F, R407A
  • Extremely low noise ...
  • High performance (COP) thanks to optimised internal media flow dynamics, the use of high-performance motors and the introduction of the latest generation of components
  • Operation with all conventional refrigerants: R448A/R449A, R404A/R507A, R134a, R407C, R407F, R407A
  • Extremely low noise emissions
  • Optimal mass balance reduces vibrations
  • Gas pressure fluctuations reduced
  • Control using different frequencies
  • IP 65 protection class as standard on most models in the series

show more


Accessories / Replacement parts

  • Additional ventilator
    Dorin additional fan f. H290CS-H743CC 230V 1ACS840
    Order No.: 112.3670
  • Crankcase heater
    Dorin oil sump heater 230V H40CC-H3400CC 2EG2020
    Order No.: 112.3808
  • Motor protection
    Dorin motor protection device INT69 internal (2CC4010) 2CC3110
    Order No.: 112.3821
  • Refrigerator oil
    Parker refrigerator oil RL 32 H 1L
    Order No.: 531.2818
  • Parker refrigerator oil RL 32 H can 5L
    Order No.: 531.2822
  • Parker refrigerator oil RL 32 H 20L
    Order No.: 531.2816

Technical data

General information
Number of cylinders
2 pcs
Type
halbhermetisch
Refrigerant
R134a
 
R450A
 
R513A
 
R404A
 
R507A
 
R448A
 
R449A
 
R452A
 
R454C
 
R455A
 
R407F
Series
H2
Type
H380SB
Compression type
Hubkolben
Electrical Data
Starting current (locked rotor)
34.0 A
voltage=400 V
Power consumption
1,88 kW
R134a (Taupunkt)
 
1,67 kW
R450A (Taupunkt)
 
2,01 kW
R513A (Taupunkt)
 
4,04 kW
R404A/R507A (Taupunkt)
 
3,50 kW
R448A/R449A (Taupunkt)
 
3,92 kW
R452A (Taupunkt)
 
2,93 kW
R454C (Taupunkt)
 
2,98 kW
R455A (Taupunkt)
 
3,52 kW
R407F (Taupunkt)
Power consumption
4,3 A
R134a (Taupunkt)
 
4,1 A
R450A (Taupunkt)
 
4,4 A
R513A (Taupunkt)
 
7,0 A
R404A/R507A (Taupunkt)
 
6,3 A
R448A/R449A (Taupunkt)
 
6,8 A
R452A (Taupunkt)
 
5,5 A
R454C (Taupunkt)
 
5,6 A
R455A (Taupunkt)
 
6,3 A
R407F (Taupunkt)
Supply voltage
400/3/50 V/Ph/Hz
max. operating current
7.5 A
voltage=400 V
Weight
Weight net
56,0 kg
Performance data
Flow volume
19,53 m³/h
at 1450 rpm-1
Pipe connections
Pressure line
16s mm
s = solder
Suction line
28s mm
s = solder
Sound data
Sound power level
69,0 dB(A)
(see explanation 1)
Volume
Oil charge
RL32H
Oil quantity
1,4 l

Note

  1. The excellent results from Dorin have been “certified” by stringent measurement of the dose output by the University of Florence in accordance with ISO 9614-1, level 2. Alongside the power and noise emission data given below, acoustic spectra for various frequencies are available on request. The formula for calculating the acoustic pressure (Lp) at a given distance (d) and known acoustic power (Lw) is: Lp = Lw + 10 Log [K/ (4x3.142 x d x d)], where K = directional efficiency = 1 for open space, d = distance in metres
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.
Loading

Login now for complete access

To login
Delivery item. Delivery time on request