- Products
- Air conditioners & ventilation systems
- Convectors
- for water
- Standing units
- Arbonia chest unit Condiline DXC ECM 63 2-wire,3 RR MO
Standing units
Arbonia chest unit Condiline DXC ECM 63 2-wire,3 RR MO
Icon. Image similar to product.
Order No.: 778.130312
Manufacturer number: DXC36301200X02A
Manufacturer: Arbonia
More in this category: Standing units
Loading
One click to the most important information:
Description
The Arbonia Condiline DXC and DXC ECM cabinet units are available in many different versions for a wide variety of applications. One of the main advantages of these devices is their exceptional quietness of operation. It features a sturdy supporting frame as you would expect. The units are ...
The Arbonia Condiline DXC and DXC ECM cabinet units are available in many different versions for a wide variety of applications. One of the main advantages of these devices is their exceptional quietness of operation. It features a sturdy supporting frame as you would expect. The units are available with or without cladding and for wall-mounting or ceiling installation. Many different connection and controller options are also available.
Features
- Easy to maintain filter
- Up to 9 different size options depending on version
- Colour: Front RAL 9003, cladding Pantone Cool Grey 1C (light grey)
- AC or EC motor technology
- With radial or tangential fan
- Two or three way valve
- Two or four line system
- Important information about the technical data:
- Acoustic ...
- Easy to maintain filter
- Up to 9 different size options depending on version
- Colour: Front RAL 9003, cladding Pantone Cool Grey 1C (light grey)
- AC or EC motor technology
- With radial or tangential fan
- Two or three way valve
- Two or four line system
- Important information about the technical data:
- Acoustic pressure level: In a 100m3 space, reverberation period of 0.5 s, spatial damping factor 9 dB(A)
- Acoustic power level according to Eurovent
- Air inlet temperature: dry bulb +27 °C, wet bulb +19 °C
- For temperatures different to those for the given data (water 7-12 °C), multiply the figures with the factors specified in the catalogue below.
Technical data
Dimensions
Height
530 mm
without feet
630 mm
with feet
Depth
225 mm
General information
Version
2-Leiter
Type
für Wasser
Construction
Truhengerät
Performance data
Inverter control voltage 1 V
Pressure loss water
6,3 kPa
Total cooling capacity
2,12 kW
Air volume
305 m³/h
Sensitive cooling capacity
1,46 kW
Inverter Steuerspannung 1 V
Wasserdurchfluss
365 l/h
Inverter control voltage 10 V
Pressure loss water
21,6 kPa
Total cooling capacity
4,29 kW
Air volume
735 m³/h
Sensitive cooling capacity
3,10 kW
Inverter Steuerspannung 10 V
Wasserdurchfluss
738 l/h
Inverter control voltage 3 V
Pressure loss water
9,1 kPa
Total cooling capacity
2,63 kW
Air volume
395 m³/h
Sensitive cooling capacity
1,84 kW
Inverter Steuerspannung 3 V
Wasserdurchfluss
453 l/h
Inverter control voltage 5 V
Pressure loss water
12,6 kPa
Total cooling capacity
3,16 kW
Air volume
495 m³/h
Sensitive cooling capacity
2,23 kW
Inverter Steuerspannung 5 V
Wasserdurchfluss
544 l/h
Inverter control voltage 7.5 V
Pressure loss water
16,8 kPa
Total cooling capacity
3,73 kW
Air volume
610 m³/h
Sensitive cooling capacity
2,66 kW
Inverter Steuerspannung 7,5 V
Wasserdurchfluss
641 l/h
Nominal cooling capacity
3,16 kW
Inverter Steuerspannung 5 V (mittel)
Fan data
Fan motor
EC
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.
Loading
Loading