The Arbonia Condiline DXC and DXC ECM cabinet units are available in many different versions for a wide variety of applications. One of the main advantages of these devices is their exceptional quietness of operation. It features a sturdy supporting frame as you would expect. The units are ...
The Arbonia Condiline DXC and DXC ECM cabinet units are available in many different versions for a wide variety of applications. One of the main advantages of these devices is their exceptional quietness of operation. It features a sturdy supporting frame as you would expect. The units are available with or without cladding and for wall-mounting or ceiling installation. Many different connection and controller options are also available.
Features
- Easy to maintain filter
- Up to 9 different size options depending on version
- Colour: Front RAL 9003, cladding Pantone Cool Grey 1C (light grey)
- AC or EC motor technology
- With radial or tangential fan
- Two or three way valve
- Two or four line system
- Important information about the technical data:
- Acoustic ...
- Easy to maintain filter
- Up to 9 different size options depending on version
- Colour: Front RAL 9003, cladding Pantone Cool Grey 1C (light grey)
- AC or EC motor technology
- With radial or tangential fan
- Two or three way valve
- Two or four line system
- Important information about the technical data:
- Acoustic pressure level: In a 100m3 space, reverberation period of 0.5 s, spatial damping factor 9 dB(A)
- Acoustic power level according to Eurovent
- Air inlet temperature: dry bulb +27 °C, wet bulb +19 °C
- For temperatures different to those for the given data (water 7-12 °C), multiply the figures with the factors specified in the catalogue below.
Technical data
Dimensions
Height
530 mm
without feet
630 mm
with feet
Depth
225 mm
General information
Version
2-Leiter
Type
für Wasser
Construction
Truhengerät
Performance data
Inverter control voltage 1 V
Pressure loss water
6,3 kPa
Total cooling capacity
2,12 kW
Air volume
305 m³/h
Sensitive cooling capacity
1,46 kW
Inverter Steuerspannung 1 V
Wasserdurchfluss
365 l/h
Inverter control voltage 10 V
Pressure loss water
21,6 kPa
Total cooling capacity
4,29 kW
Air volume
735 m³/h
Sensitive cooling capacity
3,10 kW
Inverter Steuerspannung 10 V
Wasserdurchfluss
738 l/h
Inverter control voltage 3 V
Pressure loss water
9,1 kPa
Total cooling capacity
2,63 kW
Air volume
395 m³/h
Sensitive cooling capacity
1,84 kW
Inverter Steuerspannung 3 V
Wasserdurchfluss
453 l/h
Inverter control voltage 5 V
Pressure loss water
12,6 kPa
Total cooling capacity
3,16 kW
Air volume
495 m³/h
Sensitive cooling capacity
2,23 kW
Inverter Steuerspannung 5 V
Wasserdurchfluss
544 l/h
Inverter control voltage 7.5 V
Pressure loss water
16,8 kPa
Total cooling capacity
3,73 kW
Air volume
610 m³/h
Sensitive cooling capacity
2,66 kW
Inverter Steuerspannung 7,5 V
Wasserdurchfluss
641 l/h
Nominal cooling capacity
3,16 kW
Inverter Steuerspannung 5 V (mittel)
Fan data
Fan motor
EC