Outdoor units

Panasonic air conditioning PACi outdoor unit Elite PZH U-200PZH2E8 20kW R32

Order No.: 758.2242
Manufacturer number: U-200PZH2E8
Manufacturer: Panasonic

To previous product 758.1443

More in this category: Outdoor units

Loading

One click to the most important information:

Description

It's not just good wines that need very specific conditions so that they mature just right. Other types of product also need to be stored below normal room temperatures:
- Flower shops
- Storage and sale of fruit and vegetables
- Pharmacies / medicine storage rooms (pharmacy regulations)

Using ...

It's not just good wines that need very specific conditions so that they mature just right. Other types of product also need to be stored below normal room temperatures:
- Flower shops
- Storage and sale of fruit and vegetables
- Pharmacies / medicine storage rooms (pharmacy regulations)

Using the Panasonic PACi ELITE series, these special temperature conditions are efficiently and affordably achieved. A constant room temperature of 8 °C is not a problem.
Panasonic allows you to achieve the appropriate climatic conditions for private and commercial applications in any room, regardless of its size and layout.

show more


Features

  • Compatible with many different models of indoor unit
  • Low investment costs
  • Inverter technology for energy efficiency
  • Wide range of products from 3.50 kW to 23.20 kW

Suitable products
Concealed duct unit with high compression
Panasonic air conditioner PACi concealed duct unit PE S-200PE3E5 20kW (high pressure)

Panasonic air conditioner PACi concealed duct unit PE S-200PE3E5 20kW (high pressure)

Order No.: 758.2602
Indoor unit 4-way cassette
Panasonic air conditioner PACi 4W cassette without cover PU S-140PU2E5B 14kW (840x840mm)

Panasonic air conditioner PACi 4W cassette without cover PU S-140PU2E5B 14kW (840x840mm)

Order No.: 758.2181
Indoor unit ceiling suspended unit
Panasonic air conditioner PACi ceiling PT S-140PT2E5B 14kW

Panasonic air conditioner PACi ceiling PT S-140PT2E5B 14kW

Order No.: 758.2189
Indoor unit concealed duct unit
Panasonic air conditioner PACi concealed duct unit PF S-140PF1E5B 14kW

Panasonic air conditioner PACi concealed duct unit PF S-140PF1E5B 14kW

Order No.: 758.2197
Pufferspeicher
Panasonic PRO HT buffer tank f. heating and cooling water PAW-VP380L

Panasonic PRO HT buffer tank f. heating and cooling water PAW-VP380L

Order No.: 758.2624

Accessories / Replacement parts

  • Inverterplatine
    Panasonic inverter board HIC PACi U-200PZH2E8 HIC
    Order No.: 758.2757
  • Sichtschutzgehäuse
    Evolar Sichtschutz Gehäuse Tower Lamellen Anthrazit 1600x1200x650mm
    Order No.: 732.5001
  • Evolar Sichtschutz Gehäuse Tower Lamellen Weiss 1600x1200x650mm
    Order No.: 732.5002
  • Weatherproof hood
    Panasonic air conditioner accessories PACi PAW-WPH5-A weatherproof hood U200-250PZH
    Order No.: 758.2647

Technical data

Dimensions
Width
980 mm
explanation 2
Height
1500 mm
Depth
370 mm
General information
Type
Professional
Construction
Außengerät
Refrigerant
R32
Amount of refrigerant
4,20 kg
max. height difference
indoor unit/outdoor unit
30 m
explanation 1
max. pre-filled line length
30 m
zul. Leitungslänge
(min. - max.)
5 - 80 m
permissible filling quantity per meter
60 g/m
Electrical Data
Recommended overcurrent relay
16 A
Supply voltage
400/3/50 V/Ph/Hz
max. power consumption
13,5 A
Weight
Weight net
117,0 kg
Performance data
Design load
Heating
17,00 kW
at -10 °C
Air volume
Heating (high)
9840 m³/h
Cooling (high)
9840 m³/h
Nominal heating capacity
22,40 kW
Nominal cooling capacity
19,50 kW
Nominal power consumption
Heating
6,21 kW
Cooling
6,06 kW
SCOP
4,84
explanation 3
SEER
5,25
explanation 3
Pipe connections
Liquid line
9,52 mm
3/8 inch
Suction gas line
25,40 mm
1 Zoll
Sound data
Sound pressure level
Heating (high)
61 dB(A)
Cooling (high)
59 dB(A)
Sound power
Heating (high)
79 dB(A)
Cooling (high)
77 dB(A)
Temperature data
Außentemperatur-­Grenzwerte
Heizen
-20 bis +24 °C
Kühlen
-15 bis +46 °C

Notes

  1. Outdoor unit placed higher than indoor unit. Please note: Filters are not included.
  2. For the line connection, add 100 mm to the indoor unit and 70 mm to the outdoor unit.
  3. SEER/SCOP values are calculated according to EU Regulation 626/2011 for models with a rated power up to 12 kW and EU Regulation 2281/2016 for models with a rated power above 12 kW.
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.