Outdoor units

Panasonic air conditioner outdoor unit PACi elite PZH U-71PZH2E5 7,1kW 230V R32

Order No.: 758.2208
Manufacturer number: U-71PZH2E5
Manufacturer: Panasonic

To previous product 758.1456
To subsequent product 758.2272

Loading

One click to the most important information:

Description

Its not just good wines that need very specific conditions so that they mature just right. Other types of product also need to be stored below normal room temperatures:
- Flower shops
- Storage and sale of fruit and vegetables
- Pharmacies / medicine storage rooms (pharmacy regulations)

Using ...

Its not just good wines that need very specific conditions so that they mature just right. Other types of product also need to be stored below normal room temperatures:
- Flower shops
- Storage and sale of fruit and vegetables
- Pharmacies / medicine storage rooms (pharmacy regulations)

Using the Panasonic PACi ELITE series, these special temperature conditions are efficiently and affordably achieved. A constant room temperature of 8 °C is not a problem.
Panasonic allows you to achieve the appropriate climatic conditions for private and commercial applications in any room, regardless of its size and layout.

show more


Features

  • Compatible with many different models of indoor unit
  • Low investment costs
  • Inverter technology for energy efficiency
  • Wide range of products from 3.50 kW to 23.20 kW

Suitable products
Indoor unit - 4-way cassettes
Panasonic air conditioner PACi 4W cassette without cover PU S-71PU2E5B 7.1kW (840x840mm)

Panasonic air conditioner PACi 4W cassette without cover PU S-71PU2E5B 7.1kW (840x840mm)

Order No.: 758.2178
Indoor unit - ceiling suspended unit
Panasonic air conditioner PACi ceiling PT S-71PT2E5B 7.1kW

Panasonic air conditioner PACi ceiling PT S-71PT2E5B 7.1kW

Order No.: 758.2186
Indoor unit - concealed duct unit
Panasonic air conditioner PACi concealed duct unit PF S-71PF1E5B 7.1kW

Panasonic air conditioner PACi concealed duct unit PF S-71PF1E5B 7.1kW

Order No.: 758.2194
Indoor unit
Panasonic air conditioner PACi wall PK S-71PK2E5B 7.1kW

Panasonic air conditioner PACi wall PK S-71PK2E5B 7.1kW

Order No.: 758.2169

Accessories / Replacement parts

  • Other accessories
    Panasonic inverter board HIC PACi U-71PZH2E5
    Order No.: 758.2752

Technical data

Dimensions
Width
940 mm
Height
996 mm
Depth
340 mm
General information
Connectable indoor units
2
Energy efficiency­class
Heating
A++
Cooling
A++
Refrigerant
R32
Amount of refrigerant
1,95 kg
max. height difference
indoor unit/outdoor unit
30 m
explanation 5
max. pre-filled line length
30 m
zul. Leitungslänge
(min. - max.)
5 - 50 m
permissible filling quantity per meter
45 g/m
Electrical Data
Supply voltage
230/1/50 V/Ph/Hz
max. power consumption
17,5 A
Weight
Weight net
68 kg
Performance data
Design load
Heating
5,20 kW
at -10 °C
Cooling
7,10 kW
Annual power consumption
Heating
1549 kWh/a
explanation 3
Cooling
365 kWh/a
explanation 3
Air volume
Heating (high)
3600 m³/h
Cooling (high)
3660 m³/h
Nominal heating capacity
8,00 kW
Nominal cooling capacity
7,10 kW
Nominal power consumption
Heating
2,00 kW
Cooling
2,03 kW
SCOP
4,70
explanation 2
SEER
6,80
explanation 2
Pipe connections
Liquid line
9,52 mm
3/8 inch
Suction gas line
15,88 mm
5/8 inch
Sound data
Sound pressure level
Heating (high)
50 dB(A)
explanation 4
Cooling (high)
48 dB(A)
explanation 4
Sound power
Heating (high)
67 dB(A)
Cooling (high)
65 dB(A)
Temperature data
Außentemperatur-­Grenzwerte
Heizen
-20 bis +24 °C
Kühlen
-15 bis +46 °C

Notes

  1. EER/COP values are calculated based on EN14511.
  2. SEER/SCOP values are calculated according to EU Regulation 626/2011 for models with a rated power up to 12 kW and EU Regulation 2281/2016 for models with a rated power above 12 kW.
  3. The annual power consumption is calculated based on the specifications in EU Regulation 626/2011.
  4. Measurement locations - indoor unit: 1 m in front of and 1 m below the unit. The measured values are based on EUROVENT document 6/C/006-97.
  5. Outdoor unit placed higher than indoor unit. * A fuse of 3 A is recommended for the indoor unit.
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.
Loading

Login now for complete access

To login