- FAQ
- Fault code ECOi ME1 & MF1
- General questions
- Wish Lists, shopping baskets & offers
- Create offer for end customer
- Manage users
- To search & find
- Information & purchasing
- error codes
- Fault codes for RAC and semi-FS inverter units
- Fault code ECOi ME1 & MF1
- Fault codes FS devices
- Fault code ECOi ME2 & MF2
- Meine Auswertungen
- Explanatory videos
- Features mySchiessl
- Störungscodes Single-/Multi-Split
- Störungscodes PACi NX
Fault code ECOi ME1 & MF1
Meaning of the fault | Outdoor unit could not receive communication signals from the indoor unit | |||
Preconditions | Outdoor unit cannot receive communication signals from the indoor unit | |||
Possible causes |
| |||
Check as a priority | Check the power supply on the indoor and outdoor units and the control lines between the units. | |||
Example | - | |||
Notes | This alarm is recognised after the initial communication is complete. For this reason, it does not occur if the connector is not connected, the terminal unit is not set, or other problems have occurred before the initial communication is completed. If the initial communication has not been completed, alarm E04 occurs. |
Meaning of the fault | The automatic start of the address setting is not permitted. | |||
Preconditions | The automatic address setting was started when the automatic address setting was carried out on another outdoor unit in the same connection. | |||
Possible causes | The automatic address setting is carried out on another outdoor unit. | |||
Priority check | This alarm is not displayed on the remote control. Therefore, check the blinking on the outdoor unit circuit board. | |||
Correction | Then restart the automatic address setting. Wait for the automatic address setting on the outdoor unit on which it is currently being performed to complete. | |||
Example | – | |||
Note | – |
Meaning of the fault | Alarm for automatic address setting (too few units) | |||
Alarm conditions | The number of indoor units was too few when the automatic address setting was carried out. | |||
Probable cause |
| |||
Priority check |
| |||
Correction | After you adjust the quantity of the indoor unit or the wiring between the control units, carry out the automatic address setting again. | |||
Example | – | |||
Note | 2 way exchange control |
Meaning of the fault | Alarm for automatic address setting (too many units) | |||
Alarm conditions |
| |||
Probable cause |
| |||
Check |
| |||
Correction | After you adjust the quantity of the indoor unit or the wiring between the control units, carry out the automatic address setting again. |
Meaning of the fault | No indoor units with automatic address setting. | |||
Preconditions | No indoor units were recognised with the automatic address setting | |||
Possible causes |
| |||
Priority check |
| |||
Correction | Reconnect the control cable between the units from the outdoor unit to the indoor unit. | |||
Example | – | |||
Note | Position of the CN001 serial connector to 2 pin |
Meaning of the fault | Outdoor unit (INV) was unable to receive communication from another outdoor unit (constant speed). | |||
Conditions | After the first communication, communication from an outdoor unit was stopped. | |||
Possible causes |
|
Meaning of the fault | Meaning of the error Error when setting the address of the outdoor unit (duplication). | |||
Preconditions | were received five times or more times through communication over the main sub-control wiring of the outdoor unit that has the same address as this unit. | |||
Possible causes | The device number is set incorrectly. | |||
Priority check | Check the unit number again. | |||
Correction | – | |||
Example | – | |||
Note | Restoration after this alarm is automatic (if there is no communication with the same address for 3 minutes). |
Meaning of the fault | Mismatch in the quantity of outdoor units. | |||
Preconditions | After the power initialisation, the set number of outdoor units did not match the number of outdoor units for 3 minutes or more which were recognised on the main-secondary control line of the outdoor unit. | |||
Possible causes. |
| |||
Priority check. |
| |||
Correction |
| |||
Example | – | |||
Note | Restoration after this alarm is automatic (if the set outdoor unit quantity matches the number of outdoor units recognised by the main-secondary control wiring of the outdoor unit). |
Meaning of the fault | Outdoor unit could not receive communication from the outdoor unit (main unit) | |||
Preconditions | Communication of the outdoor unit from the outdoor unit (main unit) was interrupted for at least 3 minutes. | |||
Possible causes |
| |||
Priority check |
| |||
Correction |
|
Meaning of the fault | Communication error between two microcomputers on the control circuit board | |||
Preconditions | – | |||
Possible causes | It happens:
| |||
Priority check |
| |||
Correction | Replace the control circuit board |
Meaning of the fault | Compressor 1 Fault in the outlet temperature sensor | |||
Preconditions |
| |||
Possible causes |
| |||
Priority check | 1. Sensor malfunction and outdoor unit circuit board failure Always shows a high temperature.
Wiggle the sensor and check if the error persists. 2. Crossed wiring or installation error Although the other compressor is operating and this compressor is stopped, the outlet temperature of the other compressor does not rise and the outlet temperature of this compressor increases.
Check: Check for wiring and installation errors. 3. Leakage at the outlet pipe check valve Although the other compressor is operating and this compressor is stopped, the outlet temperature of this compressor rises along with the temperature of the other compressor. 4. The ambient temperature around the outdoor unit, when it is stopped, is 43°C or more. 5. If after checking the above items the cause is still unknown, it is possible that electrical noise is the cause of the problem. It is necessary to provide a line filter or take other countermeasures against noise. | |||
Correction |
| |||
Example | Sensor wiring is partially cut. | |||
Note | This alarm does not indicate that the sensor is not connected. To avoid overheating during operation, the outdoor units in this system do not allow a compressor to start unless the outlet temperature decreases while the compressor is stopped. If a malfunction of the sensor leads to the continuous detection of a high outlet temperature, the compressor may stop for no apparent reason. The purpose of this alarm is to make it easier to identify the problem in this case. |
Meaning of the fault | Compressor 2 Fault on the outlet temperature sensor | |||
Preconditions |
| |||
Possible causes |
| |||
Priority check | 1. Sensor malfunction and outdoor unit circuit board failure Always shows a high temperature.
Wiggle the sensor and check if the error persists. 2. Crossed wiring or installation error Although the other compressor is operating and this compressor is stopped, the outlet temperature of the other compressor does not rise and the outlet temperature of this compressor increases.
Check: Check for wiring and installation errors. 3. Leakage at the outlet pipe check valve Although the other compressor is operating and this compressor is stopped, the outlet temperature of this compressor rises along with the temperature of the other compressor. 4. The ambient temperature around the outdoor unit, when it is stopped, is 43°C or more. 5. If after checking the above items the cause is still unknown, it is possible that electrical noise is the cause of the problem. It is necessary to provide a line filter or take other countermeasures against noise. | |||
Correction |
| |||
Example | Sensor wiring is partially cut. | |||
Note | This alarm does not indicate that the sensor is not connected. To avoid overheating during operation, the outdoor units in this system do not allow a compressor to start unless the outlet temperature decreases while the compressor is stopped. If a malfunction of the sensor leads to the continuous detection of a high outlet temperature, the compressor may stop for no apparent reason. The purpose of this alarm is to make it easier to identify the problem in this case. |
Meaning of the fault | Gas temperature sensor fault on the outdoor heat exchanger 1 | |||
Preconditions |
| |||
Possible causes |
| |||
Priority check |
|
Meaning of the fault | Gas temperature sensor fault on the outdoor heat exchanger 1 | |||
Preconditions |
| |||
Possible causes |
| |||
Priority check |
|
Meaning of the fault | Problem with the outside air temperature sensor | |||
Preconditions |
| |||
Possible causes |
| |||
Priority check |
|
Meaning of the fault | Compressor intake temperature sensor defective | |||
Preconditions |
| |||
Possible causes |
| |||
Priority check |
|
Meaning of the fault | High pressure sensor fault (abnormal increase in high pressure) (In some cases, this cannot be attributed to a malfunction of the high pressure sensor.) Preconditions | |||
Preconditions |
| |||
Possible causes |
| |||
Priority check | 1. High pressure sensor failure
* The pressure detected by the high pressure sensor is the highest pressure in the system. Therefore, the converted saturation temperature during heating will never be lower than the internal E1 temperature. During cooling, this temperature is never lower than the outdoor unit fluid temperature.
2. The service valve cannot be opened, the hoses are blocked, the valve is leaking and it is overloaded.
* The representative valves to be checked are the fluid valves and the mechanical valves. 3. Outdoor unit PCB failure
| |||
Correction | 1. Replace the high pressure sensor. 2. Replace the circuit boards. 3. Correct the points where problems occur in the refrigeration circuit. Correct areas where blockages or leaks have occurred. | |||
Example | This alarm can occur when the service valve is closed or when there is a valve leak (especially from the mechanical valve). | |||
Note | – |
Meaning of the fault | Problem with the low pressure sensor
| |||
Preconditions |
| |||
Possible causes |
| |||
Priority check |
|
Meaning of the fault | Compressor 3 Fault on the outlet temperature sensor | |||
Preconditions |
| |||
Possible causes |
| |||
Priority check | 1. Sensor malfunction and outdoor unit circuit board failure Always shows a high temperature.
Wiggle the sensor and check if the error persists. 2. Crossed wiring or installation error Although the other compressor is operating and this compressor is stopped, the outlet temperature of the other compressor does not rise and the outlet temperature of this compressor increases.
Check: Check for wiring and installation errors. 3. Leakage at the outlet pipe check valve Although the other compressor is operating and this compressor is stopped, the outlet temperature of this compressor rises along with the temperature of the other compressor. 4. The ambient temperature around the outdoor unit, when it is stopped, is 43°C or more. 5. If after checking the above items the cause is still unknown, it is possible that electrical noise is the cause of the problem. It is necessary to provide a line filter or take other countermeasures against noise. | |||
Correction |
| |||
Example | Sensor wiring is partially cut. | |||
Note | This alarm does not indicate that the sensor is not connected. To avoid overheating during operation, the outdoor units in this system do not allow a compressor to start unless the outlet temperature decreases while the compressor is stopped. If a malfunction of the sensor leads to the continuous detection of a high outlet temperature, the compressor may stop for no apparent reason. The purpose of this alarm is to make it easier to identify the problem in this case. |
Meaning of the fault | Gas temperature sensor fault on the outdoor heat exchanger 2 | |||
Preconditions |
| |||
Possible causes |
| |||
Priority check |
|
Meaning of the fault | Fluid temperature sensor fault on the outdoor heat exchanger 2 | |||
Preconditions |
| |||
Possible causes |
| |||
Priority check |
|
Meaning of the fault | Default of the solid-state memory (EEPROM) of the outdoor unit | |||
preconditions |
| |||
Possible causes |
| |||
Priority check | Check the solid-state memory on the circuit board. |
Meaning of the error | CT sensor of compressor 1 not connected or short-circuited | |||
Preconditions | The current value at compressor 1 was 18 A or less- No current is detected, even though the compressor is in operation | |||
Possible causes |
| |||
Priority check | 1. CT circuit failure, PCB failure Problem: The current value during compressor operation is below the threshold. Check: 2. Crossed wiring or installation error Problem: If the compressor is stopped, the actual value on the other compressor is high. 3. If after checking the above items the cause is still unknown, it is possible that the noise is the cause of the problem. It is necessary to connect a PC or other instrument
| |||
Correction |
| |||
Example |
| |||
Note | Use a normal transformer to help determine whether the problem is a circuit board fault or a transformer fault. |
Meaning of the fault | Discharge temperature sensor of compressor 1 not connected | |||
Preconditions |
| |||
Possible causes |
| |||
Priority check |
| |||
Correction |
| |||
Example | – | |||
Note | The outlet temperature sensor is generally a sensor designed to accurately detect high temperatures. Therefore, the temperature is not accurately measured when the temperature at the measuring point is 20°C or less. |
Alarm meaning | Low pressure switch activated | |||
Alarm conditions | During A / C operation, a message is issued when the low pressure sensor installed on parts with constant low pressure continuously detects a pressure of 0.05 MPa or less or an instantaneous pressure of 0.02 MPa or less for 2 minutes. (These values represent an unusually low pressure that can damage the compressor.) | |||
Possible causes | The vacuum in the air conditioning system has dropped to a level that no longer occurs under normal conditions.
☆ When the alarm occurs when there is sufficient refrigerant in the system ((1) and (3)), the liquid refrigerant has definitely accumulated somewhere in the system. Liquid refrigerant generally accumulates in high pressure locations. In this case, the high pressure gradually increases (but cannot increase if the location where the liquid accumulates is sufficiently large). Depending on the refrigerant saturation temperature, it can also accumulate in places with low pressure. In this case, it is unlikely that the high pressure will increase. | |||
Priority check: |
| |||
Correction |
|
Meaning of the fault | Fault (open circuit) on the oil sensor (connection) to compressor 1 | |||
Preconditions | This alarm occurs when a plug connection (pins 1 and 2 for compressor 1) is open. | |||
Possible causes | Plug may be disconnected | |||
Check as a priority | Check whether the plug is firmly connected. | |||
Correction |
|
Meaning of the fault | Overcurrent alarm for compressor 2 with constant rpm | |||
Preconditions | During operation, the compressor current exceeded 12 A for at least 30 seconds. However, if this alarm goes off 4 seconds after the compressor starts it will not be recognised During operation, the compressor current has exceeded 14 A for at least 4 seconds. However, this alarm is not recognised 2 seconds after the compressor has started | |||
Possible causes |
| |||
Priority check | 1. Compressor failure (partially locked) Problem: The current value during operation considerably exceeds the value specified above. Test: If the current for each phase is measured with a clamp meter or similar instrument, check that the current value for all phases is not high. If MG has been switched on (caution), make sure that no compressor noises occur or that the compressor does not run with a groaning noise. 2. CT circuit failure, PCB failure Check: 3. Missing power phase problem: This alarm mainly occurs when the T phase is missing. If the R phase or S phase is missing, transformer or PCB continuity problems arise. However, this may not apply in the event of a missing phase caused by a magnetic SW error. Check: There is a possibility of a magnetic SW error. Therefore, check the phase voltage in a location as close as possible to the compressor. 4. Low voltage problem: In most cases, this occurs when another constant speed compressor (including compressors in other units) or another unit is started. This also occurs when the power cables are extremely long. Test: Check the voltage between the individual phases. However, if this occurs when starting other units or compressors, an oscilloscope is required. 5. PCB error Test: Ensure that the current value measured with the clamp meter is not below the value measured with the PC or the remote control 6. If after checking the above items the cause is still unknown, it is possible that noise is the cause of the problem. It is necessary to connect a PC or other instrument | |||
Correction: | Replace the compressor. |
Meaning of the error | Current alarm for compressor with constant speed and 2 locks
| |||
Preconditions | During operation, the compressor current exceeded 12 A for at least 30 seconds. However, this alarm is not recognised 4 seconds after the compressor has started | |||
Possible causes |
| |||
Priority check | 1. Compressor failure (partially locked) Problem: The current value during operation considerably exceeds the value specified above. Test: If the current for each phase is measured with a clamp meter or similar instrument, check that the current value for all phases is not high. If MG has been switched on (caution), make sure that no compressor noises occur or that the compressor does not run with a groaning noise. 2. CT circuit failure, PCB failure Check: 3. Missing power phase problem: This alarm mainly occurs when the T phase is missing. If the R phase or S phase is missing, transformer or PCB continuity problems arise. However, this may not apply in the event of a missing phase caused by a magnetic SW error. Check: There is a possibility of a magnetic SW error. Therefore, check the phase voltage in a location as close as possible to the compressor. 4. Low voltage problem: In most cases, this occurs when another constant speed compressor (including compressors in other units) or another unit is started. This also occurs when the power cables are extremely long. Test: Check the voltage between the individual phases. However, if this occurs when starting other units or compressors, an oscilloscope is required. 5. PCB error Test: Ensure that the current value measured with the clamp meter is not below the value measured with the PC or the remote control. 6. If after checking the above items the cause is still unknown, it is possible that noise is the cause of the problem. It is necessary to connect a PC or other instrument | |||
Correction: | Replace the compressor. |
Meaning of the fault | CT sensor for compressor 2 not connected or short-circuited | |||
Conditions | The current value at compressor 2 was 2 A or less. No current is detected even though the compressor is in operation | |||
Possible causes |
| |||
Priority check | 1. CT circuit failure, PCB failure Problem: The current value during compressor operation is below the threshold. Check: 2. Crossed wiring or installation error Problem: If the compressor is stopped, the actual value on the other compressor is high. 3. If after checking the above items the cause is still unknown, it is possible that the noise is the cause of the problem. It is necessary to connect a PC or other instrument
| |||
Correction |
| |||
Example |
| |||
Note | Use a normal transformer to help determine whether the problem is a circuit board fault or a transformer fault. |
Meaning of the fault | Discharge temperature sensor of compressor 2 not connected | |||
Preconditions |
| |||
Possible causes |
| |||
Priority check |
| |||
Correction |
| |||
Example | – | |||
Note | The outlet temperature sensor is generally a sensor designed to accurately detect high temperatures. Therefore, the temperature is not accurately measured when the temperature at the measuring point is 20°C or less. |
Meaning of the fault | Overcurrent alarm for compressor 3 with constant rpm | |||
Preconditions | During operation, the compressor current exceeded 12 A for at least 30 seconds. However, if this alarm goes off 4 seconds after the compressor starts it will not be recognised During operation, the compressor current has exceeded 14 A for at least 4 seconds. However, this alarm is not recognised 2 seconds after the compressor has started | |||
Possible causes |
| |||
Priority check | 1. Compressor failure (partially locked) Problem: The current value during operation considerably exceeds the value specified above. Test: If the current for each phase is measured with a clamp meter or similar instrument, check that the current value for all phases is not high. If MG has been switched on (caution), make sure that no compressor noises occur or that the compressor does not run with a groaning noise. 2. CT circuit failure, PCB failure Check: 3. Missing power phase problem: This alarm mainly occurs when the T phase is missing. If the R phase or S phase is missing, transformer or PCB continuity problems arise. However, this may not apply in the event of a missing phase caused by a magnetic SW error. Check: There is a possibility of a magnetic SW error. Therefore, check the phase voltage in a location as close as possible to the compressor. 4. Low voltage problem: In most cases, this occurs when another constant speed compressor (including compressors in other units) or another unit is started. This also occurs when the power cables are extremely long. Test: Check the voltage between the individual phases. However, if this occurs when starting other units or compressors, an oscilloscope is required. 5. PCB error Test: Ensure that the current value measured with the clamp meter is not below the value measured with the PC or the remote control 6. If after checking the above items the cause is still unknown, it is possible that noise is the cause of the problem. It is necessary to connect a PC or other instrument | |||
Correction: | Replace the compressor. |
Meaning of the fault | Compressor with constant speed 3 blocks the current alarm
| |||
Preconditions | During operation, the compressor current has exceeded 14 A for at least 4 seconds. However, this alarm is not recognised 2 seconds after the compressor has started | |||
Possible causes |
| |||
Priority check | 1. Compressor failure (partially locked) Problem: The current value during operation considerably exceeds the value specified above. Test: If the current for each phase is measured with a clamp meter or similar instrument, check that the current value for all phases is not high. If MG has been switched on (caution), make sure that no compressor noises occur or that the compressor does not run with a groaning noise. 2. CT circuit failure, PCB failure Check: 3. Missing power phase problem: This alarm mainly occurs when the T phase is missing. If the R phase or S phase is missing, transformer or PCB continuity problems arise. However, this may not apply in the event of a missing phase caused by a magnetic SW error. Check: There is a possibility of a magnetic SW error. Therefore, check the phase voltage in a location as close as possible to the compressor. 4. Low voltage problem: In most cases, this occurs when another constant speed compressor (including compressors in other units) or another unit is started. This also occurs when the power cables are extremely long. Test: Check the voltage between the individual phases. However, if this occurs when starting other units or compressors, an oscilloscope is required. 5. PCB error Test: Ensure that the current value measured with the clamp meter is not below the value measured with the PC or the remote control. 6. If after checking the above items the cause is still unknown, it is possible that noise is the cause of the problem. It is necessary to connect a PC or other instrument | |||
Correction: | Replace the compressor. |
Meaning of the fault | CT sensor for compressor 3 not connected or short-circuited | |||
Conditions | The current value at compressor 3 was 2 A or less. No current is detected even though the compressor is in operation | |||
Possible causes |
| |||
Priority check | 1. CT circuit failure, PCB failure Problem: The current value during compressor operation is below the threshold. Check: 2. Crossed wiring or installation error Problem: If the compressor is stopped, the actual value on the other compressor is high. 3. If after checking the above items the cause is still unknown, it is possible that the noise is the cause of the problem. It is necessary to connect a PC or other instrument
| |||
Correction |
| |||
Example |
| |||
Note | Use a normal transformer to help determine whether the problem is a circuit board fault or a transformer fault. |
Meaning of the fault | Discharge temperature sensor of compressor 3 not connected | |||
Preconditions |
| |||
Possible causes |
| |||
Priority check |
| |||
Correction |
| |||
Example | – | |||
Note | The outlet temperature sensor is generally a sensor designed to accurately detect high temperatures. Therefore, the temperature is not accurately measured when the temperature at the measuring point is 20°C or less. |
Meaning of the fault | Fault (open circuit) on the oil sensor (connection) to compressor 2 | |||
Preconditions | This alarm occurs when a plug connection (pins 4 and 5 for compressor 2) is open. | |||
Possible causes | Plug may be disconnected | |||
Priority check | Check whether the plug is firmly connected. | |||
Correction |
|
Meaning of the fault | Fault (open circuit) on the oil sensor (connection) to compressor 3 | |||
Preconditions | This alarm occurs when a plug connection (pins 7 and 8 for compressor 3) is open. | |||
Possible causes | Plug may be disconnected | |||
Priority check | Check whether the plug is firmly connected. | |||
Correction |
|
Meaning of the fault | HIC malfunction detector | |||
Preconditions | This alarm occurs when the microcomputer detects an error signal (indicating an abnormal HIC temperature or other problems) from the HIC. The HIC assesses the current and the temperature and outputs the error signal. In general, this indicates problems with the HIC itself. | |||
Possible causes | Overcurrent in the HIC circuit and the resulting abnormal warming caused by a HIC error | |||
Priority check | Check the power and connection cables. If the wiring and connections are normal, use a tester to measure the resistance between the HIC performance of the compressor (HIC +) and ground (HIC–). | |||
Correction | If a HIC fault is found, replace the circuit board. | |||
Example | – | |||
Note | Switch The power supply and check the continuity of HIC + and HIC– on the HIC board. |
Meaning of the fault | Double system address outdoors | |||
Possible causes | Incorrect address settings of the outdoor system | |||
Priority check | Check the settings of the system address again | |||
Correction | Correct the system address settings. | |||
Example | – | |||
Note | Restoration after this alarm is automatic (if the communication containing the same address as this device is not received 3 minutes after detection). |
Meaning of the fault | Capacity of the outdoor unit not set | |||
Preconditions | The capacity of the outdoor unit has not been set or the setting is not permitted by the system. | |||
Possible causes | This alarm occurs because the capacity has not been set. | |||
Priority check | Check if code 81 is incorrect. Use the remote control to maintain the outdoor unit and set it properly. * After changing the setting, make sure that you reset both the indoor and outdoor voltage. | |||
Correction |
| |||
Example | – | |||
Note | The remote control for servicing the outdoor unit is required to set the capacity in the EEPROM of the outdoor unit. |
Meaning of the fault | Outdoor unit model not matching | |||
Preconditions | This alarm occurs when a device other than a refrigerant R410A model is connected. Probable cause | |||
Possible causes |
| |||
Priority check |
| |||
Correction | – | |||
Example | – | |||
Note | The remote controller for maintenance of the outdoor unit is required to set the refrigerant type in the EEPROM of the outdoor unit. |
Meaning of the fault | 4-way valve actuation error | |||
Preconditions | While heating (Comp. ON), the highest detected temperature on a heat exchanger of the outdoor unit (EXG 1, EXG 2, EXL 1 or EXL 2) was 20°C or more above the outside air temperature (air temp.) continuously for 5 minutes or longer or the recorded intake temperature (SCT) was 20°C or more above the outside air temperature continuously for 5 minutes or longer. | |||
Possible causes |
| |||
Priority check |
| |||
Correction | If the connector is normal, correct or replace the problem locations. |
Alarm meaning | The thermal protection of the compressor is activated. (trigger only and no alarm) | |||
Preconditions | If the current is not detected for 4 seconds after the compressor is switched on. | |||
Possible causes | Activation state of the thermal protection of the compressor (the voltage between phase L and N is more than 260 V or less than 160 V) | |||
Priority check |
| |||
Correction |
|
Meaning of the fault | Problems with compressor 1 outlet temperature | |||
Preconditions | The temperature is 106°C or more and there was a stop before triggering. The alarm occurs when the stop occurs more than once before triggering. However, the flow counter is cleared if the compressor runs continuously for a certain period of time. | |||
Possible causes |
| |||
Priority check | 1. Capillary blockage problem: The compressor outlet temperature does not drop even if the liquid valve is switched on. If the fluid valve is in operation and the liquid valve is switched on, check whether the secondary side of the liquid capillaries is cold. 2. Too little refrigerant problem: The fluid effect is bad Test: Check whether or not the superheat temperature drops when the mechanical valve of the evaporator is opened to 300 pulses or more (after checking for foreign matter). 3. Contamination by foreign bodies Problem: The effectiveness of the fluid valve is poor Control: Make sure that there is no difference in condensation or frost conditions between the primary and secondary tubes of the strainer. 4. Crossed thermistor problem: The outlet temperature of the other compressor is high, although only this compressor is in operation. When the liquid valve turns on, the outlet temperature of the other compressor drops. 5. Accumulation of refrigerant in stopped outdoor units Problem: Check: 6. Sensor defective Test: 7. If the cause is not known after checking the above points, it is possible that the electrical noise is the cause of the fault. | |||
Correction |
| |||
Example | All probable causes | |||
Note | Works continuously for a set period of time. Shows 2.5 minutes or more for an inverter unit and 30 seconds or more for a constant speed compressor |
Meaning of the fault | High pressure switch activated. | |||
Preconditions | The operation of the electronic circuit in the high pressure switch can short-circuit the connection depending on the pressure. The terminal is short-circuited at a pressure of 3.3 MPa or more. As soon as the connection is short-circuited, it remains in this state until the pressure drops below 2.6 MPa. | |||
Possible causes |
| |||
Check as a priority. | 1. Make sure that the high pressure switch connector is correctly connected. | |||
Correction | Replace damaged components and correct the amount of refrigerant charged |
Meaning of the fault | Reverse phase (or missing phase) detected. | |||
Preconditions | This alarm occurs when an inverted phase or a missing phase is detected in phases L1-L2-L3-N. | |||
Possible causes | Phase reversal or missing phase in phases L1-L2-L3-N. | |||
Priority check | The wiring on the power terminal plate. | |||
Correction | Change phases and plug in again. Check if the result is in order |
Meaning of the fault | O2 sensor operation | |||
Preconditions |
| |||
Possible causes | – | |||
Priority check |
|
Meaning of the fault | Overcurrent alarm for compressor 1 (INV). | |||
Conditions | This alarm occurs when a current fault or a current detection fault occurs (when a fault judgment current is detected in the primary or secondary current or if an instantaneous secondary current of 18 A * or higher is detected). If more than the overcurrent values in the primary and secondary current specified in the table have been determined. Primary secondary If more than the current values specified in the table are immediately detected in the secondary current. Second | |||
Possible causes | There is a strong possibility of a compressor failure. An alarm for current detection problems occurs when it is determined that no current is flowing after the start (DCCT is damaged). In this case, the cause is a DCCT error. | |||
Priority check | Check the power and connector wiring. | |||
Correction | It is possible to solve this problem by limiting the maximum frequency. |
Meaning of the fault | Problems with compressor 2 outlet temperature | |||
Preconditions | The temperature is 106°C or more and there was a stop before triggering. The alarm occurs when the stop occurs more than once before triggering. However, the flow counter is cleared if the compressor runs continuously for a certain period of time. | |||
Possible causes |
| |||
Priority check | 1. Capillary blockage problem: The compressor outlet temperature does not drop even if the liquid valve is switched on. If the fluid valve is in operation and the liquid valve is switched on, check whether the secondary side of the liquid capillaries is cold. 2. Too little refrigerant problem: The fluid effect is bad Test: Check whether or not the superheat temperature drops when the mechanical valve of the evaporator is opened to 300 pulses or more (after checking for foreign matter). 3. Contamination by foreign bodies Problem: The effectiveness of the fluid valve is poor Control: Make sure that there is no difference in condensation or frost conditions between the primary and secondary tubes of the strainer. 4. Crossed thermistor problem: The outlet temperature of the other compressor is high, although only this compressor is in operation. When the liquid valve turns on, the outlet temperature of the other compressor drops. 5. Accumulation of refrigerant in stopped outdoor units Problem: Check: 6. Sensor defective Test: 7. If the cause is not known after checking the above points, it is possible that the electrical noise is the cause of the fault. | |||
Correction |
| |||
Example | All probable causes | |||
Note | Works continuously for a set period of time. Shows 2.5 minutes or more for an inverter unit and 30 seconds or more for a constant speed compressor |
Meaning of the fault | Problems with compressor 3 outlet temperature | |||
Preconditions | The temperature is 106°C or more and there was a stop before triggering. The alarm occurs when the stop occurs more than once before triggering. However, the flow counter is cleared if the compressor runs continuously for a certain period of time. | |||
Possible causes |
| |||
Priority check | 1. Capillary blockage problem: The compressor outlet temperature does not drop even if the liquid valve is switched on. If the fluid valve is in operation and the liquid valve is switched on, check whether the secondary side of the liquid capillaries is cold. 2. Too little refrigerant problem: The fluid effect is bad Test: Check whether or not the superheat temperature drops when the mechanical valve of the evaporator is opened to 300 pulses or more (after checking for foreign matter). 3. Contamination by foreign bodies Problem: The effectiveness of the fluid valve is poor Control: Make sure that there is no difference in condensation or frost conditions between the primary and secondary tubes of the strainer. 4. Crossed thermistor problem: The outlet temperature of the other compressor is high, although only this compressor is in operation. When the liquid valve turns on, the outlet temperature of the other compressor drops. 5. Accumulation of refrigerant in stopped outdoor units Problem: Check: 6. Sensor defective Test: 7. If the cause is not known after checking the above points, it is possible that the electrical noise is the cause of the fault. | |||
Correction |
| |||
Example | All probable causes | |||
Note | Works continuously for a set period of time. Shows 2.5 minutes or more for an inverter unit and 30 seconds or more for a constant speed compressor |
Meaning of the fault | High load fault | |||
Preconditions | The high pressure rise is not quick, but the alarm occurs if the power does not reach the expected time downwards. | |||
Possible causes |
| |||
Priority check | Check the valve, the mechanical valve and the outside fan. |
Meaning of the fault | Fan motor problems | |||
Preconditions | Fan motor start fault, fan motor Hall IC input fault. | |||
Possible causes | Hall IC input circuit fault or on Fan HIC failure. | |||
Priority inspection | Check fan motor wiring, Hall IC wiring, and connector connections. | |||
Correction | If the fan does not start, the following corrections can be effective.
| |||
Example | – | |||
Note | Switch off the power supply and check the continuity of "+" and "-" on the fan circuit board. |
Meaning of the fault | Inverter compressor has phase or blocking alarm. | |||
Preconditions | This alarm can occur at start-up and occurs if a missing phase or lock is detected and if a DCCT error occurs. | |||
Possible causes | Alarm Generally, this alarm occurs when the refrigerant pressure equalisation is uneven at startup or when the inverter compressor locks up, there is no phase in the inverter compressor wiring, or a DCCT error occurs. This can be interpreted as a start-up problem that is not caused by HIC. | |||
Priority check | Check the power and connector cabling. | |||
Correction | DCCT error (replace board) or compressor error | |||
Example | – | |||
Note | Use a tester to measure the voltage between the DCCT output on the back of the PCB and the earth. If the voltage is not within 2 - 3 V, the DCCT is malfunctioning. |