2-way

Alco solenoid valve without coil 240 RA 12T7 M 22mm solder

Order No.: 244.0125
Manufacturer number: 801170
Manufacturer: Alco

More in this category: 2-way

One click to the most important information:

Features

  • For all fluorinated refrigerants. Closed when power off. Not for NH3!

  • Compact design with fast clips for attaching the coil (coil not included, please order separately!)

  • Series 110 positively controlled, series 200 & 240 servo-controlled

  • Series 200 RB 4 to 240 RA 16 with manual opening spindle ...

  • For all fluorinated refrigerants. Closed when power off. Not for NH3!

  • Compact design with fast clips for attaching the coil (coil not included, please order separately!)

  • Series 110 positively controlled, series 200 & 240 servo-controlled

  • Series 200 RB 4 to 240 RA 16 with manual opening spindle (type suffix M) on request

  • Series 240 RA 20 comes with an manual opening spindle as standard

show more


Technical data

General information
Type
240 RA 12T7M
Pressure
max. operating pressure
35 bar
Opening differential pressure
0,05 bar
Performance data
Throughput
KV value
5,4 m³/h
Nominal capacity
Liquid
85.7 kW
refrigerant=R 134A
 
59.5 kW
refrigerant=R 507A
 
88.1 kW
refrigerant=R 407C
Hot gas
39.4 kW
refrigerant=R 134A
 
41.1 kW
refrigerant=R 507A
 
50.5 kW
refrigerant=R 407C
Suction gas
9.9 kW
refrigerant=R 134A
 
10.9 kW
refrigerant=R 507A
 
12.3 kW
refrigerant=R 407C
Pipe connections
Solder
22
mm
 
7/8"
inch
Temperature data
Media temperature
-40 bis +120 °C
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.
Loading

Login now for complete access

To login
Delivery item. Delivery time on request