2-way

Danfoss solenoid valve with coil EVR15 16mm solder 032F219331

Order No.: 244.0418
Manufacturer number: 032F219331
Manufacturer: Danfoss

One click to the most important information:

Features

  • For all fluorinated refrigerants

  • Conditionally for CO2 (up to 45 bar)

  • Valves with solder connection need not be removed before soldering
  • EVR2 and EVR3 directly controlled, all others servo-controlled (minimum drop in pressure 0.05/0.07 bar)

  • Models EVR15 to 40 are available with a manual opening ...

  • For all fluorinated refrigerants

  • Conditionally for CO2 (up to 45 bar)

  • Valves with solder connection need not be removed before soldering
  • EVR2 and EVR3 directly controlled, all others servo-controlled (minimum drop in pressure 0.05/0.07 bar)

  • Models EVR15 to 40 are available with a manual opening spindle on request (special order)

  • Models EVR15 and 20 are also available with a flanged connection (special order)

  • Max. opening pressure differential: EVR2 = 25 bar, all others = 21 bar (at 230 V / 50 Hz





show more


Accessories / Replacement parts

  • Repair kit
    Danfoss repair kit f. EVR15 Version 1 032F0187
    Order No.: 244.0451
  • Sealing set
    Danfoss seal kit for EVR2-3 & 10-20 Version 1/2 032F8196
    Order No.: 244.0722

Technical data

Pressure
max. operating pressure
32 bar
Opening differential pressure
0,05 bar
Performance data
Throughput
KV value
2,6 m³/h
Nominal capacity
Liquid
48,3 kW
refrigerant=R 134A
 
36,5 kW
refrigerant=R 404A
 
36,5 kW
refrigerant=R 507A
 
49,16 kW
refrigerant=R 407C
Hot gas
19 kW
refrigerant=R 134A
 
19,6 kW
refrigerant=R 404A
 
19,6 kW
refrigerant=R 507A
 
23,28 kW
refrigerant=R 407C
Suction gas
4.2 kW
refrigerant=R 134A
 
5,3 kW
refrigerant=R 404A
 
5,3 kW
refrigerant=R 507A
 
5,43 kW
refrigerant=R 407C
Pipe connections
Solder
16 mm
Temperature data
Media temperature
-40 bis +105 °C
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.
Loading

Login now for complete access

To login