- Products
- Refrigeration components
- Regulators
- Electronic
- Motor protection units
- Kriwan motor protection device INT69 diagnose 22A414S82
Kriwan motor protection device INT69 diagnose 22A414S82
More in this category: Motor protection units
One click to the most important information:
Description
The INT69-2 Diagnose motor protection is a further development of the existing KRIWAN trigger device. Using additional protective functions that respond flexibly, increased availability and a longer service life of the refrigeration system is achieved. The INT69-2 Diagnose stores operating and ...
?xml>The INT69-2 Diagnose motor protection is a further development of the existing KRIWAN trigger device. Using additional protective functions that respond flexibly, increased availability and a longer service life of the refrigeration system is achieved. The INT69-2 Diagnose stores operating and fault data in non-volatile memory. This data can be exported to a PC and analysed for diagnostic purposes. The full scope of diagnostic options is achieved by using the KRIWAN-specific AMS sensor.
This trigger device is primarily used with compressors that are certified according to IEC/EN 60335.
Features
Static: When the rated trigger temperature of the integrated
AMS or PTC sensors is reached, an immediate shut-off occurs.
Dynamic: If the temperature increases unusually fast,
the motor is immediately switched off, even if the temperature is still
far below the trigger temperature. This ...
Static: When the rated trigger temperature of the integrated
AMS or PTC sensors is reached, an immediate shut-off occurs.
Dynamic: If the temperature increases unusually fast,
the motor is immediately switched off, even if the temperature is still
far below the trigger temperature. This prevents high excess temperatures.
Temperature measurement circuit
- Type: 1-2 AMS sensors according to DIN 44081, DIN 44082 in series, alternatively 1-9 PTC sensors according to DIN 44081, DIN 44082 in series
- R25, total<1.8 kΩ
- Rtrigger, static 4.5 kΩ ±20%
- Reset 2.75 kΩ ±20%
- Max. length of connection line: 30 m
- Motor temperature, static: 1 min ±12s
- Motor temperature, dynamic: 5min ±1min