- Products
- Refrigeration components
- Regulators
- Electronic
- Accessories / spare parts
- Kriwan level monitoring 230V INT 276 LC+ 52S476S62
Kriwan level monitoring 230V INT 276 LC+ 52S476S62
More in this category: Accessories / spare parts
One click to the most important information:
Description
Light pulses from the device are blocked by liquid and
reflected in gaseous environments. This allows the INT276 LC+ to
reliably determine the fill level.
Level monitoring starts 3 seconds after activating the power supply. Delayed responses prevent incorrect switching caused by brief ...
Light pulses from the device are blocked by liquid and
reflected in gaseous environments. This allows the INT276 LC+ to
reliably determine the fill level.
Level monitoring starts 3 seconds after activating the power supply. Delayed responses prevent incorrect switching caused by brief variations in the liquid level.
If the level gets too low or there is a fault, the relay switches off. Once the correct level is again reached or the fault is cleared, the relay turns on again.
The neutral make contact can be inserted directly into a safety chain without needing an auxiliary relay. Integrated self-monitoring provides increased operation reliability, installation checks ensure proper assembly.
An in-built LED indicates the current status (see blink codes).
Features
Switching delay
- After activating power supply: 3s ±1s
- Level incorrect or fault: 5s ±2s
- Level good and no fault: 5s ±2s
- Mechanical service life: Approx. 1 million switching cycles
- Connection type Cable 4x x AWG 18/7