Without logging

Pego Schaltkasten elektronisch 230V ECP 200 Expert Pulse mit 2 NTC Fühlern

Order No.: 272.2465
Manufacturer number: SP1P200EXP-PULSE
Manufacturer: Pego

More in this category: Without logging

One click to the most important information:

Description

The scope of delivery includes 1 pc control board with display and keyboard for operating elements, 1 pc NTC sensor 10K 1% 1.5 m for room, 1 pc NTC sensor 10K 1% 3 m for evaporator and loose screw connections.

ECP 202 Expert with technical optimizations!

ECP 202 Expert is a microprocessor ...

The scope of delivery includes 1 pc control board with display and keyboard for operating elements, 1 pc NTC sensor 10K 1% 1.5 m for room, 1 pc NTC sensor 10K 1% 3 m for evaporator and loose screw connections.

ECP 202 Expert with technical optimizations!

ECP 202 Expert is a microprocessor controlled refrigeration system controller for the control of room temperature, evaporator fans and defrost heating. The actual temperature is displayed on a three-digit LED display. The refrigeration control has five independent relay outputs, for compressor, evaporator fan, defrost heater, alarm output and cold room light. In addition, the ECP 202 Expert refrigeration control has two potential-free input contacts (door contact switch and compressor protection), which can be configured accordingly. The switching states of the individual outputs are shown on the display. Programming of the refrigeration system control is carried out via the keys located on the front panel. Furthermore, the ECP 202 Expert refrigeration control system has two NTC sensor inputs for determining the room temperature and the evaporator temperature. Sensor break and sensor short circuit are indicated in the display.

Design:
Conform to general directives and standards, such as:
CE, EN 61000-6-1 EN 61000-6-3 EN 60335 - 1.
In pump-down mode, the LP pressostat is connected to the digital input
(terminal INP-1 and INP-GND). The solenoid valve is connected to the AUX /Alarm relay. Parameter AU is set to 4.

show more


Features

  • The ECP Plus 202 Expert may only be commissioned by trained specialist personnel

  • Changes to the device can affect safety.

  • It is essential to note the type of voltage on the rating plate.

  • The manufacturer assumes no liability in the event of modifications to or improper handling of the devices.


Accessories / Replacement parts

  • Accessories / spare parts
    Pego Softwaretreiber Anbindung Xweb SW-EXP-WEB
    Order No.: 272.2464

Technical data

Dimensions
Width
263 mm
Height
180 mm
Depth
96 mm
General information
Housing
ABS Kunststoff
Measurement inputs
2 x NTC Fühler 10K 1%
Electrical Data
Pulse-Ventil
50 VA
triac Relais
Protection class
IP65
Supply voltage
230/1/50 V/Ph/Hz
max. power consumption
Defrost heating
16 A
explanation 1
Alarm relay
8 A
Refrigeration cell lighting
16 A
explanation 1
Evaporator fan (AC3)
2,7 A
explanation 1
Compressor
10 A
explanation 1
Humidity
Humidity measurement range
<90 %rh
Weight
Weight net
2,0 kg
Temperature data
Storage temperature
-10 bis +70 °C
Umgebungstemperatur
max.
50 °C
min.
-5 °C

Erläuterungen

  1. Die Summe der gleichzeitigen Aufnahmen der Verbraucher darf 16A nicht überschreiten.
  2. Die ECP Plus 200 Expert darf nur von geschultem Fachpersonal in Betrieb genommen werden.
  3. Änderungen am Gerät können die Sicherheit beeinträchtigen.
  4. Spannungsart unbedingt dem Typenschild entnehmen.
  5. Bei Änderungen oder unsachgemäßer Handhabung der Geräte, wird keine Haftung vom Hersteller übernommen.
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.