Split

Panasonic heat pump LT outdoor unit 230V WH-UD03JE5 heating / cooling 3.2kW

Order No.: 758.2227
Manufacturer number: WH-UD03JE5
Manufacturer: Panasonic

To subsequent product 758.3190

Loading

One click to the most important information:

Description

The AQUAREA range of air/water heat pumps is the largest on the market and ensures that there is always a suitable system available for a wide range of heating and cooling requirements.
With its new 3rd generation, Panasonic combines the tried-and-tested benefits of AQUAREA with the advantages ...

The AQUAREA range of air/water heat pumps is the largest on the market and ensures that there is always a suitable system available for a wide range of heating and cooling requirements.
With its new 3rd generation, Panasonic combines the tried-and-tested benefits of AQUAREA with the advantages of environmentally friendly refrigerant R32.

show more


Features

  • SCOP up to +5% compared to the H generation
  • Waster inlet temperature up to 60 °C
  • Improved pipe lengths
  • Cooling function down to 10 °C outdoor temperature
  • Improved comfort with extremely low temperatures: Heating curve can be set down to -20 °C
  • Efficiency and comfort modes for hot tap ...
  • SCOP up to +5% compared to the H generation
  • Waster inlet temperature up to 60 °C
  • Improved pipe lengths
  • Cooling function down to 10 °C outdoor temperature
  • Improved comfort with extremely low temperatures: Heating curve can be set down to -20 °C
  • Efficiency and comfort modes for hot tap water: Partial power for better efficiency or full power to reduce the warm up time
  • 2 sensor settings for hot tap water with combi hydro module: Efficiency (best COP) or a higher hot water flow rate
  • Quiet outdoor units
  • Magnetic filter for the water circuit
  • SG ready
  • PV function for cooling
  • Bivalent control via external isolated contact
  • Lock an external devices (e.g. ventilation fan) during the defrosting phase via external isolated contact

show more


Suitable products
Combi hydro module
Panasonic heat pump LT combi-hydromodule WH-ADC0309J3E5 heating / cooling 230V

Panasonic heat pump LT combi-hydromodule WH-ADC0309J3E5 heating / cooling 230V

Order No.: 758.2571
Hydromodul Splitsystem
Panasonic heat pump LT hydromodule WH-SDC0305J3E5 heating/cooling 3-5KW

Panasonic heat pump LT hydromodule WH-SDC0305J3E5 heating/cooling 3-5KW

Order No.: 758.2669
Kompakt-Kombi-Hydromodul
Panasonic heat pump LT combi-hydromodule WH-ADC0309J3E5C compact

Panasonic heat pump LT combi-hydromodule WH-ADC0309J3E5C compact

Order No.: 758.2721

Accessories / Replacement parts

  • 3-Wege-Umschaltventil-Set
    Panasonic heat pump tap water valve CZ-NV1 3-way-valve f. gen.H
    Order No.: 758.1849
  • 3-way valve
    Panasonic 3-way valve f. tap water External valve f. tank
    Order No.: 758.2728
  • Additional circuit board
    Panasonic heat pump additional circuit board CZ-NS4P Control function for generation H
    Order No.: 758.1850
  • Anschluss-Montagesatz für Kombi-Hydromodule
    Panasonic heat pump flexible pipes PAW-ADC-PREKIT-H f.combi-hydro (J+H-Gen)
    Order No.: 758.2722
  • Gehäuseheizung
    Panasonic heat pump casing heating CZ-NE2P for type 3 and 5kW
    Order No.: 758.1664
  • Interface
    Panasonic heat pump communication system CZ-TAW1 interface control via internet
    Order No.: 758.1861
  • Memory
    Panasonic heat pump water reservoir 200L enamelled, without 3-way valve
    Order No.: 758.2649
  • Panasonic heat pump water reservoir 300L enamelled, without 3-way valve
    Order No.: 758.2650
  • Panasonic heat pump water reservoir 200 L stainless steel, without 3-way valve HE
    Order No.: 758.1889
  • Panasonic heat pump water reservoir 300 L stainless steel, without 3-way valve HE
    Order No.: 758.1891
  • Pufferspeicher
    Panasonic heat pump volume expansion PAW-BTANK50L-2 stainless steel
    Order No.: 758.2679
  • Raumthermostat
    Panasonic heat pump room thermostat PAW-A2W-RTWIRED cable, LCD/weekly timer
    Order No.: 758.1696
  • Panasonic heat pump room thermostat PAW-A2W-RTWIRELESS radio, LCD/weekly timer
    Order No.: 758.1697
  • Sound insulation set
    Panasonic heat pump sound insulation set CZ-UG30
    Order No.: 758.2508

Technical data

Dimensions
Width
824 mm
Height
622 mm
Depth
298 mm
General information
Application
Heizen und Kühlen
Construction
Split
Energy efficiency­class
Heating
A+++
W35
 
A++
W55
Seasonal room heating energy efficiency
200 %
W35
 
136 %
W55
Refrigerant
R32
Amount of refrigerant
0,9 kg
max. height difference
indoor unit/outdoor unit
20 m
max. pre-filled line length
10 m
zul. Leitungslänge
(min. - max.)
3 bis 25 m
permissible filling quantity per meter
20 g/m
Electrical Data
Supply voltage
230/1/50 V/Ph/Hz
Weight
Weight net
37,0 kg
Performance data
COP
5,33
(A7/W35)
 
3,64
(A2/W35)
 
2,80
(A-7/W35)
EER
3,52
(A35/W7)
 
4,85
(A38/W18)
Nominal heating capacity
3,20 kW
bei (A7/W35)
3,20 kW bei (A2/W35)
3,30 kW bei (A-7/W35)
Nominal cooling capacity
3,20 kW
bei (A35/W7)
3,20 kW bei (A35/W18)
SCOP
5.07
W35
 
3.47
W55
Pipe connections
Liquid line
6,35 mm
1/4 inch
Suction gas line
12,70 mm
1/2 inch
Sound data
Sound power level
49,1 dB(A)
(A7/W35) Flüster 3 (Erläuterung 3)
Sound power level
Heating
55.8 dB(A)
(A7/W35) Normal (explanation 3)
 
49.1 dB(A)
(A7/W35) Whisper 3 (explanation 3)
 
55 dB(A)
(A7/W55) Partial load (explanation 4)
Temperature data
Betriebsbereich Außentemperatur
Heizen
-20 bis +35 °C
Betriebsbereich Wasseraustrittstemperatur
Heizen
20 bis 60 °C
Kühlen
5 bis 20 °C

Erläuterungen

  1. Leistungsdaten bei A7/W35 und A2/W35 im Teillastbetrieb sowie bei A–7/W35 ermittelt durch ein unabhängiges Prüflabor. C3KV-Gerät bei Volllastbetrieb
  2. Schalldruckpegel des Innengeräts gemessen in 1 m Entfernung vor dem Gerät in 1,5 m Höhe bei A7/W55 im Heizbetrieb bzw. bei A35/W7 im Kühlbetrieb.
  3. Schallleistungspegel des Außengeräts bei A7/W55 im Normalbetrieb bzw. im „Flüsterbetrieb 3“ermittelt durch ein unabhängiges Prüflabor.
  4. Schallleistungspegel des Außengeräts bei A7/W55 gemäß EU-Verordnungen 811/2013 und 813/2013 sowie EN12102-1:2017.
  5. Daten lagen bei Drucklegung noch nicht vor.
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.