- Products
- L'Unite fully hermetic Condensing unit air-cooled CAJ 4452 YHR with cable and plug 230V
Fully-hermetic
L'Unite fully hermetic Condensing unit air-cooled CAJ 4452 YHR with cable and plug 230V
Icon. Image similar to product.
Order No.: 106.1556
Manufacturer number: 4.2774.30.248
Manufacturer: Tecumseh / L'Unite
To subsequent product 106.3372
One click to the most important information:
Accessories / Replacement parts
-
Mini pressure switch
-
Ventilation unit
-
Weatherproof housing
Technical data
General information
Expansion
V
refrigerant=R 134A
Type
CAJ 4452 YHR
Electrical Data
Supply voltage
230/1/50 V/Ph/Hz
Supply voltage
Fan
230/1/50
V/Ph/Hz
max. operating current
4.40 A
refrigerant=R 134A
Weight
Weight net
34,0 kg
Performance data
Refrigerating capacity
616 W
refrigerant=R 134A, ambient temperature=27 °C, evaporating temperature=-15 °C
764 W
refrigerant=R 134A, ambient temperature=27 °C, evaporating temperature=-10 °C
932 W
refrigerant=R 134A, ambient temperature=27 °C, evaporating temperature=-5 °C
1119 W
refrigerant=R 134A, ambient temperature=27 °C, evaporating temperature=0 °C
1326 W
refrigerant=R 134A, ambient temperature=27 °C, evaporating temperature=5 °C
1552 W
refrigerant=R 134A, ambient temperature=27 °C, evaporating temperature=10 °C
1796 W
refrigerant=R 134A, ambient temperature=27 °C, evaporating temperature=15 °C
567 W
refrigerant=R 134A, ambient temperature=32 °C, evaporating temperature=-15 °C
703 W
refrigerant=R 134A, ambient temperature=32 °C, evaporating temperature=-10 °C
857 W
refrigerant=R 134A, ambient temperature=32 °C, evaporating temperature=-5 °C
1029 W
refrigerant=R 134A, ambient temperature=32 °C, evaporating temperature=0 °C
1219 W
refrigerant=R 134A, ambient temperature=32 °C, evapor
Nominal capacity
0,54 A
Pipe connections
Liquid line
6,35 mm
Suction line
12,7 mm
Collector data
Collector volume
1,50 l
Sound data
Sound pressure level
69 dB(A)
Fan data
Power
22 W
Air throughput
980 m³/h
Pcs x diameter
1x250 mm
Fan speed
1350 rpm-1
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.
Loading
Login now for complete access
To login
Loading