- Arbonia chest unit Condiline DXC ECM 73 2-wire,3 RR MV
Standing units
Arbonia chest unit Condiline DXC ECM 73 2-wire,3 RR MV
Icon. Image similar to product.
Order No.: 778.130326
Manufacturer number: DXC37301415X01A
Manufacturer: Arbonia
More in this category: Standing units
Loading
One click to the most important information:
Description
The Arbonia Condiline DXC and DXC ECM cabinet units are available in many different versions for a wide variety of applications. One of the main advantages of these devices is their exceptional quietness of operation. It features a sturdy supporting frame as you would expect. The units are ...
The Arbonia Condiline DXC and DXC ECM cabinet units are available in many different versions for a wide variety of applications. One of the main advantages of these devices is their exceptional quietness of operation. It features a sturdy supporting frame as you would expect. The units are available with or without cladding and for wall-mounting or ceiling installation. Many different connection and controller options are also available.
Features
- Easy to maintain filter
- Up to 9 different size options depending on version
- Colour: Front RAL 9003, cladding Pantone Cool Grey 1C (light grey)
- AC or EC motor technology
- With radial or tangential fan
- Two or three way valve
- Two or four line system
- Important information about the technical data:
- Acoustic ...
- Easy to maintain filter
- Up to 9 different size options depending on version
- Colour: Front RAL 9003, cladding Pantone Cool Grey 1C (light grey)
- AC or EC motor technology
- With radial or tangential fan
- Two or three way valve
- Two or four line system
- Important information about the technical data:
- Acoustic pressure level: In a 100m3 space, reverberation period of 0.5 s, spatial damping factor 9 dB(A)
- Acoustic power level according to Eurovent
- Air inlet temperature: dry bulb +27 °C, wet bulb +19 °C
- For temperatures different to those for the given data (water 7-12 °C), multiply the figures with the factors specified in the catalogue below.
Technical data
Dimensions
Width
1415 mm
Height
530 mm
without feet
630 mm
with feet
Depth
225 mm
General information
Version
2-Leiter
Type
für Wasser
Construction
Truhengerät
Performance data
Inverter control voltage 1 V
Pressure loss water
11,9 kPa
Total cooling capacity
2,80 kW
Air volume
400 m³/h
Sensitive cooling capacity
1,92 kW
Inverter Steuerspannung 1 V
Wasserdurchfluss
482 l/h
Inverter control voltage 10 V
Pressure loss water
37,1 kPa
Total cooling capacity
5,36 kW
Air volume
890 m³/h
Sensitive cooling capacity
3,83 kW
Inverter Steuerspannung 10 V
Wasserdurchfluss
921 l/h
Inverter control voltage 3 V
Pressure loss water
16,5 kPa
Total cooling capacity
3,38 kW
Air volume
500 m³/h
Sensitive cooling capacity
2,34 kW
Inverter Steuerspannung 3 V
Wasserdurchfluss
581 l/h
Inverter control voltage 5 V
Pressure loss water
22 kPa
Total cooling capacity
3,98 kW
Air volume
610 m³/h
Sensitive cooling capacity
2,78 kW
Inverter Steuerspannung 5 V
Wasserdurchfluss
684 l/h
Inverter control voltage 7.5 V
Pressure loss water
29,7 kPa
Total cooling capacity
4,72 kW
Air volume
755 m³/h
Sensitive cooling capacity
3,34 kW
Inverter Steuerspannung 7,5 V
Wasserdurchfluss
812 l/h
Nominal cooling capacity
3,98 kW
Inverter Steuerspannung 5 V (mittel)
Fan data
Fan motor
EC
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.
Loading
Loading