- Products
- Air conditioners & ventilation systems
- Convectors
- for water
- Standing units
- Arbonia chest unit Condiline DXC 54+1 4-wire,1 RR (ZR) without housing IV/IO
Standing units
Arbonia chest unit Condiline DXC 54+1 4-wire,1 RR (ZR) without housing IV/IO
Icon. Image similar to product.
Order No.: 778.130217
Manufacturer number: DXC05411200X00A
Manufacturer: Arbonia
More in this category: Standing units
One click to the most important information:
Description
The Arbonia Condiline DXC and DXC ECM cabinet units are available in many different versions for a wide variety of applications. One of the main advantages of these devices is their exceptional quietness of operation. It features a sturdy supporting frame as you would expect. The units are ...
The Arbonia Condiline DXC and DXC ECM cabinet units are available in many different versions for a wide variety of applications. One of the main advantages of these devices is their exceptional quietness of operation. It features a sturdy supporting frame as you would expect. The units are available with or without cladding and for wall-mounting or ceiling installation. Many different connection and controller options are also available.
Features
- Easy to maintain filter
- Up to 9 different size options depending on version
- Colour: Front RAL 9003, cladding Pantone Cool Grey 1C (light grey)
- AC or EC motor technology
- With radial or tangential fan
- Two or three way valve
- Two or four line system
- Important information about the technical data:
- Acoustic ...
- Easy to maintain filter
- Up to 9 different size options depending on version
- Colour: Front RAL 9003, cladding Pantone Cool Grey 1C (light grey)
- AC or EC motor technology
- With radial or tangential fan
- Two or three way valve
- Two or four line system
- Important information about the technical data:
- Acoustic pressure level: In a 100m3 space, reverberation period of 0.5 s, spatial damping factor 9 dB(A)
- Acoustic power level according to Eurovent
- Air inlet temperature: dry bulb +27 °C, wet bulb +19 °C
- For temperatures different to those for the given data (water 7-12 °C), multiply the figures with the factors specified in the catalogue below.
Accessories / Replacement parts
-
Comfort flush mounted regulator EC 230 V
-
Condensate pump for horizontal installation
-
Condensate pump for vertical installation
-
Condensate tray BSO-SX
-
Condensate tray BSV-C
-
Contact sensor / Change Over sensor
-
Controller board AC motors
-
Controller board EC motors
-
External ambient temperature sensor
-
Infrared remote controls
-
Standard regulator AC 230 V
-
Standard regulator EC 230 V
-
Wall-mounted control box T-MB
Technical data
Dimensions
Width
1200 mm
Height
530 mm
with pedestal
630 mm
without pedestal
Depth
225 mm
General information
Version
4-Leiter
Type
für Wasser
Construction
Truhengerät
Performance data
Drehzahlstufe 1
Wasserdurchfluss
330 l/h
Speed level 1
Pressure loss water
8,3 kPa
Total cooling capacity
1,92 kW
Sensitive cooling capacity
1,3 kW
Speed level 2
Pressure loss water
11,8 kPa
Total cooling capacity
2,35 kW
Air volume
315 m³/h
Sensitive cooling capacity
1,59 kW
Drehzahlstufe 2
Wasserdurchfluss
404 l/h
Speed level 3
Pressure loss water
18,5 kPa
Total cooling capacity
3,03 kW
Air volume
420 m³/h
Sensitive cooling capacity
2,07 kW
Drehzahlstufe 3
Wasserdurchfluss
521 l/h
Speed level 4
Pressure loss water
23,6 kPa
Total cooling capacity
3,49 kW
Air volume
495 m³/h
Sensitive cooling capacity
2,4 kW
Drehzahlstufe 4
Wasserdurchfluss
600 l/h
Speed level 5
Pressure loss water
27,4 kPa
Total cooling capacity
3,8 kW
Air volume
545 m³/h
Sensitive cooling capacity
2,62 kW
Drehzahlstufe 5
Wasserdurchfluss
654 l/h
Speed level 6
Pressure loss water
35,5 kPa
Total cooling capacity
4,4 kW
Air volume
650 m³/h
Sensitive cooling capacity
3,06 kW
Drehzahlstufe 6
Wasserdurchfluss
757 l/h
Nominal cooling capacity
3,03 kW
Drehzahlstufe 3 (mittel)
Fan data
Fan motor
AC