Concealed duct installation units

Panasonic air conditioner VRF concealed duct unit ECOi ME2 S-280ME2E5 28KW (high pressure)

Order No.: 758.1312
Manufacturer number: S-280ME2E5
Manufacturer: Panasonic

More in this category: Concealed duct installation units

Loading

One click to the most important information:

Description

The ME2 series duct units provide a high external static pressure for excellent flexibility connecting longer air ducts with low energy consumption.
They also allow operation with 100% fresh air. Additional accessory required.
An inspection opening is to be provided by the installer on the ...

The ME2 series duct units provide a high external static pressure for excellent flexibility connecting longer air ducts with low energy consumption.
They also allow operation with 100% fresh air. Additional accessory required.
An inspection opening is to be provided by the installer on the base of the indoor unit housing (min. 450 x 450 mm).

More information can be found in the Panasonic 2019/2020 price list on page 106, or on request.

show more


Features

  • The ME2 series duct units are a flexible solution for connecting to long air ducts due to their high, adjustable external static pressure.
  • Option to use 100% fresh air
  • High degree of flexibility for designing the duct system
  • No RAP valves are required for two-line systems that do not use 100% ...
  • The ME2 series duct units are a flexible solution for connecting to long air ducts due to their high, adjustable external static pressure.
  • Option to use 100% fresh air
  • High degree of flexibility for designing the duct system
  • No RAP valves are required for two-line systems that do not use 100% fresh air
  • Increased efficiency from DC fan motors
  • Can be installed outdoors in a weatherproof housing
  • Air outlet sensor prevent cold air from being released
  • Configurable room temperature regulation

show more


Accessories / Replacement parts

  • Cable remote control
    Panasonic cable remote control PACi/ECOi CZ-RTC5B design cable remote control
    Order No.: 758.2554
  • Empfänger für IR-Fernbedienung
    Panasonic receiver f. infrared remote control concealed duct unit CZ-RWRC3 f. ECOi concealed duct unit MM1, MF2
    Order No.: 758.2611
  • HRS box
    Panasonic air conditioner VRF heat-recovery function box ECOi CZ-P160HR3 at 16kW indoor unit power
    Order No.: 758.1521
  • Infrared remote control
    Panasonic remote control infrared CZ-RWS3 f. WG MK2/PK2 and cassette MY2/PY2
    Order No.: 758.2592
  • Junction set
    Panasonic branch 2-wire f. indoor unit CZ-P680BK2BM f. ECOi ME1 6N at 22.4-68KW
    Order No.: 758.1530
  • Panasonic branch 3-wire f. indoor unit CZ-P680BH2BM f. ECOi MF2 6N at 22.4-68kW
    Order No.: 758.1535
  • RAP-Ventileinheit
    Panasonic air conditioner VRF RAP-valve unit ECOi CZ-P160RVK2 f. concealed duct unit ME1 22-28KW
    Order No.: 758.1609
  • Remote controls
    Panasonic cable remote control PACi/ECOi CZ-RTC6
    Order No.: 758.2695
  • Panasonic cable remote control PACi/ECOi CZ-RTC6BL with bluetooth function
    Order No.: 758.2696
  • WRG-Box-Steuereinheit
    Panasonic heat-recovery function box control unit CZ-CAPE2 for the other models
    Order No.: 758.1523

Technical data

Dimensions
Width
1453 mm
Height
479 mm
Depth
1205 mm
General information
Type
VRF
Construction
Kanalgerät
Refrigerant
R410A
Pressure
Static pressure
200 Pa
standard
 
140(60-270) Pa
high compression explanation 1
Weight
Weight net
106,0 kg
Performance data
Air volume
Heating (high)
2100 m³/h
standard
 
4320 m³/h
high compression
Cooling (high)
2100 m³/h
standard
 
4320 m³/h
high compression
Nominal heating capacity
26,50 kW
Standard
31,50 kW bei hoher Pressung
Nominal cooling capacity
28,00 kW
Standard
28,00 kW bei hoher Pressung
Nominal power consumption
Heating
0.350 kW
standard
 
0.715 kW
high compression
Cooling
0.350 kW
standard
 
0.715 kW
high compression
Pipe connections
Liquid line
9,52 mm
3/8 inch
Suction gas line
22,22 mm
7/8 inch
Sound data
Schalldruckpegel
Heizen
(Niedrig/Mittel/Hoch)
43 / 47 / 49 dB(A)
bei hoher Pressung (Erläuterung 2)
Kühlen
(Niedrig/Mittel/Hoch)
43 / 47 / 49 dB(A)
bei hoher Pressung (Erläuterung 2)
Sound power
Heating (high)
76 dB(A)
standard
 
81 dB(A)
high compression
Cooling (high)
76 dB(A)
standard
 
81 dB(A)
high compression

Rated conditions for operation with 100% fresh air intake: External temperature, cooling: 33 °C DB / 28 °C WB. External temperature, heating: 0 °C DB / -2.9 °C WB.

  1. Adjustable when setting up.
  2. Values apply when external static pressure is set to 140 Pa.


Please note: Filters not included. Cannot be used with ECO G GF3 3-line system.

Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.
Loading

Login now for complete access

To login
Delivery item. Delivery time on request
Optional article