- Products
- Panasonic air conditioner outdoor unit PACi elite PE U-50PE2E5A 5,0kW 230V R410A
Outdoor units
Panasonic air conditioner outdoor unit PACi elite PE U-50PE2E5A 5,0kW 230V R410A
Icon. Image similar to product.
Features
Important information about the technical data:
- Sound level measurement positions: Indoor unit: 1.5 below the ceiling, centrally beneath the unit. Outdoor unit: 1 m in front of the device at a height of 1.5 m. The measured values are based on EUROVENT document 6/C/006-97.
- The cable cross-section is based on the maximum wire lengths. For shorter lengths, the cross-section may be made smaller depending on local regulations.
- Height different between indoor and outdoor unit: first value: Outdoor unit above / second value height difference: Outdoor unit below
Important information about the technical data:
- Sound level measurement positions: Indoor unit: 1.5 below the ceiling, centrally beneath the unit. Outdoor unit: 1 m in front of the device at a height of 1.5 m. The measured values are based on EUROVENT document 6/C/006-97.
- The cable cross-section is based on the maximum wire lengths. For shorter lengths, the cross-section may be made smaller depending on local regulations.
- Height different between indoor and outdoor unit: first value: Outdoor unit above / second value height difference: Outdoor unit below
Suitable products
Technical data
Dimensions
Width
799 mm
Height
619 mm
Depth
299 mm
General information
Connectable indoor units
1
Kältemitteleinsatzbereich
R410A
Amount of refrigerant
1,4 kg
max. height difference
indoor unit/outdoor unit
30 / 15 m
max. pre-filled line length
30 m
zul. Leitungslänge
(min. - max.)
(min. - max.)
3 - 40 m
permissible filling quantity per meter
20
g/m
Electrical Data
Recommended overcurrent relay
16 A
Nominal operating current (Cooling/Heating)
6,00 / 6,10 A
Supply voltage
230/1/50 V/Ph/Hz
empfohlener Netzkabelquerschnitt
3 x 2,5 mm²
max. power consumption
12,0 A
Weight
Weight net
39 kg
Pipe connections
Liquid line
6,35 mm
1/4 inch
Suction gas line
12,70 mm
1/2 inch
Sound data
Schalldruckpegel
Heizen
(Flüster/Niedrig/Hoch)
(Flüster/Niedrig/Hoch)
46 dB(A)
Schallleistung
Heizen
(Flüster/Niedrig/Hoch)
(Flüster/Niedrig/Hoch)
- / - / 68 dB(A)
Sound power
Cooling (whisper/low/high)
- / - / 65 dB(A)
Temperature data
Air temperature
Heating
-20 bis +24 °C
Cooling
-15 bis +46 °C
Fan data
Air volume
Cooling/Heating (whisper/low/high)
2.280 / 2.460 m³/h
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.
Loading
Login now for complete access
To login
Loading