2-way

Danfoss solenoid valve with coil EVR3 6mm solder 032F205331

Order No.: 244.0412
Manufacturer number: 032F205331
Manufacturer: Danfoss

More in this category: 2-way

One click to the most important information:

Features

  • For all fluorinated refrigerants

  • Conditionally for CO2 (up to 45 bar)

  • Valves with solder connection need not be removed before soldering
  • EVR2 and EVR3 directly controlled, all others servo-controlled (minimum drop in pressure 0.05/0.07 bar)

  • Models EVR15 to 40 are available with a manual opening ...

  • For all fluorinated refrigerants

  • Conditionally for CO2 (up to 45 bar)

  • Valves with solder connection need not be removed before soldering
  • EVR2 and EVR3 directly controlled, all others servo-controlled (minimum drop in pressure 0.05/0.07 bar)

  • Models EVR15 to 40 are available with a manual opening spindle on request (special order)

  • Models EVR15 and 20 are also available with a flanged connection (special order)

  • Max. opening pressure differential: EVR2 = 25 bar, all others = 21 bar (at 230 V / 50 Hz





show more


Accessories / Replacement parts

  • Mounting bracket
    Danfoss mounting bracket EVR2,3,6,10 032F0197 (032F0086)
    Order No.: 244.0454
  • Repair kit
    Danfoss repair kit f. EVR2/3 Version 1/2 032F0181
    Order No.: 244.0448
  • Sealing set
    Danfoss seal kit for EVR2-3 & 10-20 Version 1/2 032F8196
    Order No.: 244.0722

Technical data

Pressure
max. operating pressure
45 bar
Opening differential pressure
0 bar
Opening differential pressure with standard coil
21 bar
max. MOPD 10W (AC)
Performance data
Throughput
KV value
0,27 m³/h
Nominal capacity
Liquid
5.0 kW
refrigerant=R 134A
 
3.8 kW
refrigerant=R 404A
 
3.8 kW
refrigerant=R 507A
 
5.08 kW
refrigerant=R 407C
Hot gas
2.0 kW
refrigerant=R 134A
 
2 kW
refrigerant=R 404A
 
2 kW
refrigerant=R 507A
 
2.43 kW
refrigerant=R 407C
Temperature data
Media temperature
-40 bis +105 °C
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.

Customers also bought...

Recently viewed products

Loading

Login now for complete access

To login
Article in stock