Electronic oil level regulation systems

ESK electronic oil level regulator ERM 6-OC-B

Order No.: 262.140136
Manufacturer number: ERM6-OC-B
Manufacturer: ESK Schultze

To previous product 262.140104

More in this category: Electronic oil level regulation systems

One click to the most important information:

Description

The ESK components stated are intended exclusively for use in refrigeration systems. Commissioning requires that everything has been properly installed in line with applicable legal regulations. All components have been designed and produced in line with applicable regulations.

In compressor ...

The ESK components stated are intended exclusively for use in refrigeration systems. Commissioning requires that everything has been properly installed in line with applicable legal regulations. All components have been designed and produced in line with applicable regulations.

In compressor racks, oil level regulators are attached to the compressors. Oil is supplied from a reservoir. To ensure correct functioning of the electronic regulator, all system components must be correctly designed for the performance of the system.

show more


Features

  • Aluminium body
  • Large inflow cross-sections
  • Electronics casing made of plastic
  • Inspection glass for visually checking the fill level
  • Fill level recorded independently of pressure and density
  • Normal level: Centrally positioned inspection glass
  • Opto-electronic measurement
  • Two relays for signalling and ...
  • Aluminium body
  • Large inflow cross-sections
  • Electronics casing made of plastic
  • Inspection glass for visually checking the fill level
  • Fill level recorded independently of pressure and density
  • Normal level: Centrally positioned inspection glass
  • Opto-electronic measurement
  • Two relays for signalling and recording operating state
  • Strong LEDs are less susceptible to contaminated oil
  • Integrated emergency program ensures oil supply continues even in the most difficult circumstances
  • Four measurement points allow monitoring of over- or under-filling
  • Alarm function in the event of over-filling/under-filling and if the emergency program is activated

show more


Technical data

General information
Alarm relay
250 V
 
5 A
for refrigerants
HFC/HCFC
 
R744
 
R290
 
R600a
Pressure
max. operating pressure
60 bar
max. permissible working pressure differential for oil return
1,5 bis 100 bar
max. permissible oil pressure in the oil supply line
130 bar
Electrical Data
Protection class
IP54
Supply voltage
230/1/50 V/Ph/Hz
Temperature data
max. permissible media temperature
85 °C
max. permissible ambient temperature
45 °C
Volume
Total
0,05 l
Time
Timing of oil filling
Filling/Measuring
variabel/10 s