Description
The KVP is installed in the intake line behind the evaporator. Its purpose:
1. To maintain a constant evaporating pressure and thus a constant surface temperature in the evaporator. Modulating regulation. Throttling the intake line adjusts the refrigerant volume to the load on the ...
?xml>The KVP is installed in the intake line behind the evaporator. Its purpose:
1. To maintain a constant evaporating pressure and thus a constant surface temperature in the evaporator. Modulating regulation. Throttling the intake line adjusts the refrigerant volume to the load on the evaporator.
2. Protection against the evaporating pressure being too low (e.g. to protect against freezing in a water cooler). The regulator closes if the pressure in the evaporator drops below the set value.
3. Differentiation of the evaporating pressure in a refrigeration system with a compress and several evaporators with different evaporating temperatures.
Features
Precise, adjustable pressure regulation
Wide power spectrum and range of applications
Vibration suppression
Compact angled design for easy installation in any position
“Hermetically” hard soldered design
Available in many sizes and flanged and ODF solder versions
For R 22, R 134a, R 404A, R ...
Precise, adjustable pressure regulation
Wide power spectrum and range of applications
Vibration suppression
Compact angled design for easy installation in any position
“Hermetically” hard soldered design
Available in many sizes and flanged and ODF solder versions
For R 22, R 134a, R 404A, R 12, R 502 and or fluorinated refrigerants
Regulation range: ±0 to +5.5 bar
Max. temperature: 100 °C
Approved operating pressure: 18 bar