- Produkte
- Refrigeration components
- System components
- Expansion valves
- Electronic
- Danfoss electronic expansions valve ETS 6-10 034G5005
Danfoss electronic expansions valve ETS 6-10 034G5005
More in this category: Electronic
One click to the most important information:
Description
The current product range is compact, lightweight and available in a range of different performance classes. Compatible with all common refrigerants (e.g. R410A, R407C, R404A, R507, R134a). Biflow operation possible in reversible systems such as heat pumps. The valve uses single-pole drives. ...
?xml>The current product range is compact, lightweight and available in a range of different performance classes. Compatible with all common refrigerants (e.g. R410A, R407C, R404A, R507, R134a). Biflow operation possible in reversible systems such as heat pumps. The valve uses single-pole drives. Various control solutions are available for these single-pole drives. The ETS 6 is designed for HFC/CFC conditioning (including R410A) and generates an operating pressure of 47 bar. The EIM 336, EKD 316 and MCX regulators from Danfoss are optimally designed for controlling the ETS 6. An AST-g service drive is available for manual operation and maintenance of ETS valves.
Features
- Highly precise flow volume control
Proven expertise and excellent reliability
Energy-saving design for excellent energy efficiency
Compact & lightweight hermetically closed design with replaceable coil
Biflow operation for reversible systems
Modulation: Directly controlled permanent magnet stepper ...
- Highly precise flow volume control
Proven expertise and excellent reliability
Energy-saving design for excellent energy efficiency
Compact & lightweight hermetically closed design with replaceable coil
Biflow operation for reversible systems
Modulation: Directly controlled permanent magnet stepper motor
Electrical connection: JST XHP-6 and JST XHP-5
Exciter response: min. 30 pps (pulses per second) up to max. 90 pps (recommended value: 31.3 pps)
Operating range: 0 to 480 pulses, no holding current required (NOTE: do not apply more than 520 pulses)
Installation position: With the solenoid at the top and the valve solenoid assembly tilted by a maximum of ±15˚
Solenoid valve for fluid line: When using a solenoid valve for the fluid line, it must be installed such that no hammering is caused in the ETS 6 valve
Accessories / Replacement parts
-
Connection cable
-
Connection plug
-
Display unit
-
Solenoid valve coil
-
Superheating regulator
-
Transformer