Split

MTA heat pump HCYGNUS TECH HCY071 400V

Order No.: 775.4067
Manufacturer number: .
Manufacturer: MTA

More in this category: Split

Loading

One click to the most important information:

Description

Low-noise operation of technical systems is of key importance in areas where people are always present such as apartments and offices, and the air conditioning units are generally installed very close to the user.
In order to meet the specific requirements for comfort without compromising on ...

Low-noise operation of technical systems is of key importance in areas where people are always present such as apartments and offices, and the air conditioning units are generally installed very close to the user.
In order to meet the specific requirements for comfort without compromising on performance in all operating modes, MTA has developed the HCYGNUS tech reversible heat pumps that use the environmentally friendly refrigerant R410A. The already low noise level is further reduced by the use of electronic fan speed controllers, allowing the fans to spin more slowly when the need to cool is lower.
Seasonal efficiency values are highly important when it comes to climatic comfort - and very much so in heat pump mode. Thanks to the integrated storage tank and frost detection system (FDS) that detects the quantity of ice that builds up on the external coil and only activates defrosting cycles if necessary, energy consumption is drastically reduced.

show more


Features

  • Very low noise levels;
  • High EER/COP values and high seasonal efficiency;
  • Ideal for air conditioning applications in commercial or residential premises;
  • Wide operating boundaries;
  • Optimised defrosting cycles in heating mode thanks to the unique frost detection system (FDS)I (Min. ambient ...
  • Very low noise levels;
  • High EER/COP values and high seasonal efficiency;
  • Ideal for air conditioning applications in commercial or residential premises;
  • Wide operating boundaries;
  • Optimised defrosting cycles in heating mode thanks to the unique frost detection system (FDS)I (Min. ambient temperature in heating mode -10 °C;
  • Self adaptive temperature control (SAC) for efficient system operation using a small volume of water;
  • Very compact size;
  • User-friendly intuitive controller with dual digital icon-based display;
  • Easy access to all components.

show more


Scope of delivery

• Hermetic rotary piston compressor (020), scroll compressor (031-171), tandem scroll compressors (211-301)
• Integrated hydraulic module complete with pump, tank, expansion vessel, filling and discharge valve, manometer and automatic bleed valve
• Threaded hydraulic connections ...

• Hermetic rotary piston compressor (020), scroll compressor (031-171), tandem scroll compressors (211-301)
• Integrated hydraulic module complete with pump, tank, expansion vessel, filling and discharge valve, manometer and automatic bleed valve
• Threaded hydraulic connections easily accessible on the outside of the unit
• Plate evaporator made of soldered stainless steel
• Axial fans with sickle-shaped blades and electronic speed regulation
• Heat pumps with two thermostatic valves for power optimisation in all operating conditions (models 131 to 301)
• Filled with refrigerant and refrigeration oil in the factory (except for MC versions)
• Protection class IPX4
• All products and components from MTA are approved and tested during production
• Environmentally friendly refrigerant R410A with an ozone depletion potential of 0
• Phase monitoring for controlling phase sequence
• Crankcase heater

show more


Accessories / Replacement parts

  • Commissioning
    MTA commissioning (one-time journey) f. (H)CY013 to (H)CY101
    Order No.: 775.4606

Technical data

Dimensions
Width
1420 mm
Height
1288 mm
Depth
550 mm
General information
Application
Heizen und Kühlen
Construction
Split
Energy efficiency­class
Heating
A+
explanation 6
Refrigerant
R410A
Electrical Data
Supply voltage
400/3/50 V/Ph/Hz
Weight
Circa
291 kg
with storage tank and P1 pump
Performance data
COP
3,20
explanation 5
EER
2,59
explanation 2
Nominal heating capacity
20,57 kW
(A7/W35) (Erläuterung 4)
Nominal cooling capacity
16,99 kW
(Erläuterung 1)
Nominal power consumption
Heating
6,42 kW
explanation 4
Cooling
6,57 kW
explanation 1
Sound data
Sound pressure level
49,8 dB(A)
explanation 9
Sound power level
77,8 dB(A)
explanation 8
Temperature data
max. Operating
+46 °C
explanation 3
min. operating temperature
- 7 °C
explanation 7

Notes:

  1. Nominal cooling capacity and nominal power consumption: Evaporator, water inlet / outlet temperature 12/7 °C, ambient temp. 35 °C
  2. Data is based on operation of the system under normal conditions, at full load and with an evaporator water inlet/outlet temperature of 12/7 °C and max. ambient temperature of 35 °C
  3. Data based on operating in cooling mode with water outlet temperature 7 °C
  4. Water inlet/outlet temperature 40/45 °C, relative humidity 87%, ambient temperature 7 °C;
  5. Data based on nominal conditions at full power, ambient temperature 7 °C, relative humidity 87%, condenser inlet/outlet 40/45 °C;
  6. Conforms with European Regulation 813/2013 for low temperature heat pumps (BT) on a scale of A+++ to D
  7. Data based on operating in heating mode and water outlet temperature of 45 °C;
  8. Measured data in cooling mode conforms to ISO 3744;
  9. The noise values are based on a system, incl. circulation pump, operating at full power under nominal conditions at a free field distance of 10 m, reflective surfaces, from the condenser side, at a height of 1.6 m from the ground.

 

The noise values, weights and dimensions given are for a basic system without any additional options.

 

Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.
Loading

Login now for complete access

To login
Delivery item. Delivery time on request