Description

Design safety
Certified according to the European Pressure Equipment Directive 2014/68/EU

Design features

  • Heat exchanger pipes: made from Cu or Cu-Ni (saltwater resistant version) with newly developed pipe geometry and a “low fouling” profile on the cooling medium side
  • Heat exchanger pipes ...

Design safety
Certified according to the European Pressure Equipment Directive 2014/68/EU

Design features

  • Heat exchanger pipes: made from Cu or Cu-Ni (saltwater resistant version) with newly developed pipe geometry and a “low fouling” profile on the cooling medium side
  • Heat exchanger pipes are soldered into breaker plates to ensure a secure seal
  • mantle pipes and breaker plates made from pressure vessel steel P 265 GH
  • Recirculating cap:
    - removable, allows pipes to be mechanically cleaned
    - connection and deflecting side interchangeable
    - cooling medium outlet from K573H(B)
    - additional bleeding plugs from K38 03T(B)
  • Breaker plates with plastic coating
  • Cooling medium connections: Threaded pipe or flange
  • inspection glass as standard
  • Mounting brackets
    - bottom: vessel labelled as “N”
    - top and bottom: vessel labelled as “H” (for installing single compressors) and “T” (for single and tandem compressors)
  • Refrigerant connections
    - pressurised gas: Rotalock adapter/solder connector with flange K1053H(B) and above
    - refrigerant outlet: shut-off valve
    - alternative refrigerant outlet from model K123HB
  • Rotalock connections for pressure relief valve
    - inner thread 3/a'' -18 NPTF
    - outer thread 1 ¼” - 12 UNF
  • suitable for (H)CFC / HFC refrigerants (refrigerants with a temperature glide > 2 K on request)
  • Maximum permitted pressure/temperature
    - refrigerant side: 28 bar / -10 °C to 120 °C
    - cooling medium side: 10 bar / -10 °C (with antifreeze agent) to 95 °C
  • inert gas filling

bundled pipe condensers with refrigerant outlet at the bottom can also be used as pressurised gas desuperheaters.

Special versions:

  • Salt water resistant version:
    - Cu-Ni pipe, recirculating cap with plastic coating
  • recirculating cap with plastic coating for standard version with Cu pipes
  • mounting rails or plates (e.g. for installing compressor)
  • adapter for connecting the pressure relief valve on all models
  • threaded or welding neck flange
  • refrigerant inlet and outlet with various adapter and valve combinations
  • conforms to foreign regulations and various certification societies (e.g. Bureau Veritas, Germanischer Lloyd, Lloyd's Register of Shipping)

Scope of delivery / accessories
4-pass design corresponds to standard version

Performance data
The specified compressor performance is based on valves measured at a pressurised gas temperature of 90 °C and a cooling medium cleanliness factor r= 0.4 x 1 o-4 m2 K/W.


Condenser design
Calculating of condenser capacity Q

When selecting a condenser it is first necessary to determine the condenser capacity Q. Condensing capacity can be calculated in two different ways:

Condensing capacity as the sum of the refrigeration capacity and power consumption
This method adds together the refrigeration capacity and power consumption of the compressor (or compressors in a power rack). Performance data can be found in the compressor information leaflets or in the software.

Estimation using factors
A simplified method can also be employed for typical designs. To determine condensing capacity, the refrigeration capacity of the compressor is multiplied by the factor in the following diagram.
 


 

Important note
For low temperature applications in particularly, the condenser must be sufficiently powerful such that there is a sufficient reserve of power for cooling off processes or de-icing periods (control calculation at highest evaporating temperature necessary).

show more


Accessories / Replacement parts

  • Accessories / spare parts
    Bitzer adapter for pressure relief valve 1-1/4''x1/2'-14NPTF IG
    Order No.: 101.5523
  • Bitzer adapter for pressure relief valve 1-1/4''x1/2'-14NPTF AG
    Order No.: 101.5522
  • Bitzer adapter for pressure relief valve 1-1/4''xG1/2'' AG
    Order No.: 151.7873
  • Bitzer adapter for pressure relief valve 1-1/4''xG1/2'' IG
    Order No.: 151.7872
  • Rail set bottom
    Bitzer mounting rail kit below for F252H-F902N,K573H-K813H
    Order No.: 151.7807
  • Rail set top
    Bitzer mounting rail kit above for F152 to 302H/K203H to 573HB
    Order No.: 151.7887
  • Bitzer mounting rail kit above for F252H-F1052T,K573H-K4803T
    Order No.: 151.9838
  • Upper mounting plate
    Bitzer mounting plate K203 to K4803T f.2KC-05.2 to 6F50.2
    Order No.: 151.9843

Technical data

Dimensions
Diameter
216 mm
General information
Type
Bündelrohrverflüssiger
Refrigerant charge
30.6 kg
refrigerant=R 134A
 
26.6 kg
refrigerant=R 404A
 
30.2 kg
refrigerant=R 22
Type
K813H
Condensation type
wassergekühlt
für Verdichter
4VES-6Y .. 4NES-20Y
Connections
Water outlet
2 pass
G 2 Inch
4 pass
G 11/4 Inch
Water inlet
2 pass
G 2 Inch
4 pass
G 11/4 Inch
Weight
Weight net
65,0 kg
Performance data
2 pass
Dte 10K
104700 W
Dte 15K
157100 W
4 pass
Dte 10K
87400 W
Dte 15K
131100 W
Pressure drop
2 pass
0,30 bar
4 pass
0,58 bar
max. throughput
2 pass
6.48
l/s
 
23.32
m³/h
4 pass
3.24
l/s
 
11.66
m³/h
Pipe connections
Outlet
Diameter
28 L
mm
 
11/8"
inches
Inlet
Diameter
35 L
mm
 
13/8"
inches
Rotalock connection
Rotalock thread
Outlet
1.3⁄4"-12 Inch
Inlet
1.3⁄4"-12 Inch
Volume
Content
Refrigerant side
27,7 dm³
Cooling medium side
7,0 dm³