- Produkte
- Air conditioners & ventilation systems
- Air conditioners
- VRF
- Indoor units
- Concealed duct installation units
- Mitsubishi air conditioner City Multi concealed duct unit PEFY-P40 VMS1-E (height 200mm)
Concealed duct installation units
Mitsubishi air conditioner City Multi concealed duct unit PEFY-P40 VMS1-E (height 200mm)
Icon. Image similar to product.
Order No.: 719.2376
Manufacturer number: PEFY-P40 VMS1-E
Manufacturer: Mitsubishi
More in this category: Concealed duct installation units
Loading
One click to the most important information:
Description
These duct units stand out for their low installation height. Just 200 mm is needed for installation. The external static pressure can be adjusted from 5 to 50 Pascal. This allows the unit to be flexibly adjusted to local conditions. The condensate pump is already integrated into the unit. ...
These duct units stand out for their low installation height. Just 200 mm is needed for installation. The external static pressure can be adjusted from 5 to 50 Pascal. This allows the unit to be flexibly adjusted to local conditions. The condensate pump is already integrated into the unit. Thanks to a new generation of fans, the new duct units are extremely quiet despite having an installation height of just 200 mm. They produce 22 dB(A) at the small fan stage (PEFY-P15/20/25VMS1-E).
Features
Important information about the technical data:
- Acoustic pressure level measured centrally at 1.5 m beneath the panel
- Our air conditioning systems and heat pumps contain fluorinated greenhouses gases R410A, R407C, R134a, R32.
- Further information can be found in operating manual.
Scope of delivery
- 1x Mitsubishi Klimagerät City Multi Kanal PEFY-P40VMS1-E (Höhe 200mm)
Suitable products
Accessories / Replacement parts
-
Accessories/replacement parts
-
Cable remote control
-
Central control
-
Extension module
-
Group remote control
-
Interface
Technical data
Dimensions
Width
1039 mm
Height
200 mm
Depth
700 mm
General information
Application
Kühlen und Heizen
Type
VRF
Construction
Kanalgerät
Refrigerant
R410A
Pressure
Static pressure
5/15/35/50 Pa
Electrical Data
Recommended overcurrent relay
16 A
Nennbetriebsstrom
Heizen
0,45 A
Kühlen
0,56 A
Supply voltage
230/1/50 V/Ph/Hz
Weight
Weight net
19,0 kg
Performance data
Volume flow rate
450/660 m³/h
Nominal heating capacity
5,00 kW
Nominal cooling capacity
4,50 kW
Nominal power consumption
Heating
0,03 kW
Cooling
0,05 kW
Pipe connections
Liquid line
6 mm
Gas line
12 mm
Sound data
Schalldruckpegel
Heizen
(Niedrig/Mittel/Hoch)
(Niedrig/Mittel/Hoch)
30 / 32 / 35 dB(A)
Kühlen
(Niedrig/Mittel/Hoch)
(Niedrig/Mittel/Hoch)
28 / 30 / 33 dB(A)
Schalldruckpegel
(Niedrig/Mittel/Hoch)
(Niedrig/Mittel/Hoch)
26/-/30 dB(A)
explanation 1
Erläuterungen:
- Schalldruckpegel gemessen mittig in 1,5 m Entfernung unterhalb des Gerätes.
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.
Loading
Loading