Cassette units

Panasonic air conditioner PACi 4W cassette without cover PU S-100PU2E5B 10kW(840x840mm)

Order No.: 758.2179
Manufacturer number: S-100PU2E5B
Manufacturer: Panasonic

Loading

One click to the most important information:

Description

The PU2 four-way cassette (90 x 90) sets new standards for energy-efficient operation and healthy and pleasant air. This has been possible thanks to the new design of the unit with more efficient and quieter fans and Nanoe™ X air purification.

This item does not include a ceiling panel


Features

  • Ceiling height up to 5.0 m
  • Condensate pump for delivery head up to 850 mm
  • Optional CZ-KPU3A cover with Econavi function as well as activity detection and revolving operation
  • Optional nanoe™ X air purification feature specially for commercial air conditioning systems
  • DC fan with turbo rotor: ...
  • Ceiling height up to 5.0 m
  • Condensate pump for delivery head up to 850 mm
  • Optional CZ-KPU3A cover with Econavi function as well as activity detection and revolving operation
  • Optional nanoe™ X air purification feature specially for commercial air conditioning systems
  • DC fan with turbo rotor: efficiency and quiet
  • Individual air guide slat control
  • For use in dual, trio and quattro systems there are additional models to those listed here with a power rating of 4.5 kW (see Panasonic price list from page 46).

    230 V version on request: U-100PZH2E5 758.2209 U-125PZH2E5 U-140PZH2E5

show more


Accessories / Replacement parts

  • Hotel remote control
    Panasonic cable remote control PACi/ECOi CZ-RE2C2 hotel remote control
    Order No.: 758.1561

Technical data

Dimensions
Width
840 mm
Height
319 mm
Depth
840 mm
General information
Energy efficiency­class
Heating
A++
Cooling
A++
Electrical Data
Supply voltage
230/1/50 V/Ph/Hz
Weight
Weight net
25 kg
Performance data
Design load
Heating
10,0 kW
Cooling
10,0 kW
Dehumidification
2,7 l/h
Delivery head of condensate pump
850 mm
explanation 4
Annual power consumption
Heating
2917 kWh/a
explanation 2
Cooling
461 kWh/a
explanation 2
Luftmenge
Heizen
(Niedrig/Mittel/Hoch)
1080 / 1560 / 2160 m³/h
Kühlen
(Niedrig/Mittel/Hoch)
1080 / 1560 / 2160 m³/h
Nominal heating capacity
11,2 kW
Nominal cooling capacity
10,00 kW
Nominal power consumption
Heating
2,24
Cooling
2,34 kW
SCOP
4,8
explanation 1
SEER
7,6
explanation 1
Sound data
Schalldruckpegel
Heizen
(Niedrig/Mittel/Hoch)
32 / 38 / 45 dB(A)
explanation 3
Kühlen
(Niedrig/Mittel/Hoch)
32 / 38 / 45 dB(A)
explanation 3
Schallleistung
Heizen
(Niedrig/Mittel/Hoch)
47 / 53 / 60 dB(A)
Kühlen
(Niedrig/Mittel/Hoch)
47 / 53 / 60 dB(A)

Notes

1) SEER/SCOP values are calculated according to EU Regulation 626/2011 for models with a rated power up to 12 kW and EU Regulation 2281/2016 for models with a rated power above 12 kW.
2) The annual power consumption is based on the standards in EU Regulation 626/2011.
3) Measurement locations: Indoor unit: 1.5 below the ceiling, centrally beneath the unit. Outdoor unit: 1 m in front of the device at a height of 1.5 m. The measured values are based on EUROVENT document 6/C/006-97.
4) Measured from lower edge of ceiling.

Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.