Wall-mounted units

Arbonia wall mounted unit Condiline DXA 1 3-way valve

Order No.: 778.130007
Manufacturer number: DXA01100880X20A
Manufacturer: Arbonia

More in this category: Wall-mounted units

Loading

One click to the most important information:

Description

DXA wall-mounted unit, space-saving compact unit that runs extremely quietly for use in noise-sensitive areas (bedroom, quiet zones). The DXA wall-mounted unit is optionally available with a 2 or 3-way valve, with Modbus RTU control board or with a remote control. All model variants are ...
DXA wall-mounted unit, space-saving compact unit that runs extremely quietly for use in noise-sensitive areas (bedroom, quiet zones). The DXA wall-mounted unit is optionally available with a 2 or 3-way valve, with Modbus RTU control board or with a remote control. All model variants are available with a three-phase AC or variable EC motor. Air outlet fins are automatically adjustable on all model variants with a Modbus RTU control board and the variant with remote control. Air outlet fins in housing colour, white (RAL 9003). Housing made of ABS plastic, glossy. The air outlet fins feature moveable intermediate fins that can pivot 30° in either direction to guide the flow of air to the left or right.<br><br><br>The following variants can be ordered:<br><br>DXA ECM / DXA without remote control and without valve<br>DXA ECM-2V / DXA-2V without remote control, with integrated 2-way valve<br>DXA ECM-3V / DXA-3V without remote control, with integrated 3-way valve<br><br>DXA ECM-T / DXA-T with remote control, without valve<br>DXA ECM-T-2V / DXA-T-2V with remote control and with integrated 2-way valve<br>DXA ECM-T-3V / DXA-T-3V with remote control and integrated 3-way valve<br><br>DXA ECM-MB / DXA-MB with MB control board, without valve<br>DXA ECM-MB-2V / DXA-MB-2V with MB control board and integrated 2-way valve<br>DXA ECM-MB-3V / DXA-MB-3V with MB control board and integrated 3-way valve<br><br><br>All variants can be supplied with integrated heat register. Please ask our technical specialists for performance data.

show more


Features

  • 4 sizes with overlengths of 880 and 1185 mm
  • Colour RAL 9003
  • AC or EC motor technology
  • Two or three-way valves
  • Double layer system
  • Speed level 4 = MAX (speed steps connected in the factory)
  • Speed level 2 = MED (speed steps connected in the factory)
  • Speed level 1 = MIN (speed steps connected in the ...
  • 4 sizes with overlengths of 880 and 1185 mm
  • Colour RAL 9003
  • AC or EC motor technology
  • Two or three-way valves
  • Double layer system
  • Speed level 4 = MAX (speed steps connected in the factory)
  • Speed level 2 = MED (speed steps connected in the factory)
  • Speed level 1 = MIN (speed steps connected in the factory)
  • Important information about the technical data:
  • Acoustic pressure level: In a 100m3 space, reverberation period of 0.5 s, spatial damping factor 9 dB(A)
  • Acoustic power level: According to Eurovent
  • Air inlet temperature: +27 °C, relative humidity: 50%
  • Correction coefficients for other relative humidity values:
    • 46%: Total cooling capacity: 0.90
    • 46%: Sensitive cooling capacity: 1.00
    • 48%: Total cooling capacity: 0.95
    • 48%: Sensitive cooling capacity: 1.00
  • Water temperature: °C, inlet 7 - outlet 12

show more


Technical data

Dimensions
Width
880 mm
Height
322 mm
Register size
1
Depth
212 mm
General information
Type
für Wasser
Construction
Wandgerät
Pressure
Operating pressure
10 bar
Weight
Circa
11 kg
Performance data
Drehzahlstufe 1
­Wasserdurchfluss
229 l/h
Speed level 1
Pressure loss water
5,5 kPa
Total cooling capacity
1,33 kW
Air volume
205 m³/h
Sound pressure level
44 dB(A)
Sound power level
53 dB(A)
Sensitive cooling capacity
0,91 kW
Speed level 2
Pressure loss water
7,8 kPa
Total cooling capacity
1,62 kW
Air volume
270 m³/h
Sound pressure level
43 dB(A)
Sound power level
52 dB(A)
Sensitive cooling capacity
1,13 kW
Drehzahlstufe 2
Wasserdurchfluss
279 l/h
Speed level 3
Pressure loss water
10,3 kPa
Total cooling capacity
1,89 kW
Air volume
340 m³/h
Sound pressure level
39 dB(A)
Sound power level
48 dB(A)
Sensitive cooling capacity
1,34 kW
Drehzahlstufe 3
Wasserdurchfluss
326 l/h
Speed level 4
Pressure loss water
11,6 kPa
Total cooling capacity
2,02 kW
Air volume
375 m³/h
Sound pressure level
37 dB(A)
Sound power level
46 dB(A)
Sensitive cooling capacity
1,44 kW
Drehzahlstufe 4
Wasserdurchfluss
347 l/h
Speed level 5
Pressure loss water
14,8 kPa
Total cooling capacity
2,32 kW
Air volume
470 m³/h
Sound pressure level
32 dB(A)
Sound power level
41 dB(A)
Sensitive cooling capacity
1,69 kW
Drehzahlstufe 5
Wasserdurchfluss
399 l/h
Speed level 6
Pressure loss water
15,8 kPa
Total cooling capacity
2,40 kW
Air volume
500 m³/h
Sound pressure level
26 dB(A)
Sound power level
35 dB(A)
Sensitive cooling capacity
1,76 kW
Drehzahlstufe 6
Wasserdurchfluss
413 l/h
Nominal cooling capacity
1,89 kW
Drehzahlstufe 3 (mittel)
Siehe Fußnote für Betriebsbedingungen!
Temperature data
Media temperature
6 bis 70 °C
Fan data
Fan motor
AC

Performance data is based on the following operating conditions:

COOLING (summer operation) Air temperature: +27 °C DB +19 °C WB Water temperature: +7 °C inlet+12 °C outlet

HEATING (winter operation) Air temperature: +20 °C Water temperature: +50 °C outlet
The water flow rate is the same as for summer operation

Additional performance data for operation conditions are available under downloads

Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.

Customers also bought...

Loading

Login now for complete access

To login
Delivery item. Delivery time on request