- Products
- Refrigeration components
- System components
- Valves & flanges
- Solenoid valves
- 2-way
- Castel solenoid valve with coil HF2 230V 1070/4A6 3/4"UNF (without plug)
2-way
Castel solenoid valve with coil HF2 230V 1070/4A6 3/4"UNF (without plug)
Icon. Image similar to product.
Features
For all fluorinated refrigerants
Closed when power off, with coil
Temperature of medium: -35 to +105 °C
Type 1099/11: +110 °C
Type 1078/11: 110 °C
Type 1079/M42: +110 °C
Accessories / Replacement parts
-
Repair kit
-
Union nut
Technical data
Dimensions
Nominal width
12,5 mm
General information
Type
1070/4
Pressure
max. operating pressure
45 bar
Opening differential pressure
0,05 bar
Opening differential pressure with standard coil
28 bar
max. MOPD HM4 (AC)
Weight
Weight net
0,71 kg
Performance data
Throughput
KV value
2,20 m³/h
Nominal capacity
Liquid
37.1 kW
refrigerant=R 134A
41.2 kW
refrigerant=R 407C
26.2 kW
refrigerant=R 507A
26.2 kW
refrigerant=R 404A
41.9 kW
refrigerant=R 410A
Hot gas
18.7 kW
refrigerant=R 134A
25.6 kW
refrigerant=R 407C
22.0 kW
refrigerant=R 507A
22.0 kW
refrigerant=R 404A
28.6 kW
refrigerant=R 410A
Suction gas
4.75 kW
refrigerant=R 134A
5.90 kW
refrigerant=R 407C
4.97 kW
refrigerant=R 507A
4.97 kW
refrigerant=R 404A
7.92 kW
refrigerant=R 410A
Pipe connections
Flare
3/4" UNF
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.
Loading
Loading